Appendix A – Remotes & Optional Equipment

Appendix A – Remotes and Optional Equipment

A-1 Remote 

Controls

There are several remotes that enable you to monitor and switch the inverter 
on/off from a convenient location. The remotes connect to the REMOTE port 
located on the front side of the MM Series inverter (see Figure 1-3, Item 10).
Depending on your inverter model, you can select one of the following remotes: 

MM-R

 – Provides three LED indicators for identifying inverter status, and

includes a remote ON/OFF switch (with 25’ cable). This remote is for the
MM612 model inverter (without the battery charger feature).

MM-RC

 – Provides six LED indicators for identifying inverter and charger

status, and includes a remote ON/OFF switch (with 25’ cable). This
remote is for the MM1212/MM1212-G model inverters with the battery
charger feature.

ME-RC50 

– Full feature remote with backlit LCD display and LED indicators

for identifying inverter and charger status. Provides full menu access for
easy selection and adjustment (comes with 50’ cable). The ME-RC50 is
used for many inverter models and has additional features that are not
functional with the MM Series inverter. However, it can be used with all
MM Series inverter models.

A-2

Optional Equipment and Accessories

The following Magnum components are available for use with MM Series 
inverters. Some of these items are required—depending upon the intended 
use of the inverter.

Auto Generator Start Controller

The ME-AGS-N Automatic Generator Start controller (Network version) is 
designed to automatically start your generator based on low battery condition 
or high temperature. It works with 12, 24, and 48-volt battery banks and 
includes a 4-position DIP (Dual In-line Package) switch which provides the 
ability to change the relay timing con

fi

 gurations to allow compatibility with a 

wider range of generators.

Battery Monitor Kit

The ME-BMK Battery Monitor Kit is a single battery bank amp-hour meter 
that monitors the condition of the battery and provides information to let you 
know how much energy you have available and to plan your electrical usage to 
ensure the battery is not being over-discharged. The ME-BMK-NS version does 
not include a DC shunt—order the ME-BMK to receive a 500A/50mv DC shunt.

Fuse Block/Fuses

The Magnum Fuse/Fuse-blocks are used to protect the battery bank, inverter, 
and cables from damage caused by DC short circuits and overloads. They 
include a slow-blow fuse with mounting block and protective cover. The 125 
and 200-amp models use an ANL type fuse and the 300 and 400-amp models 
use a Class-T fuse.

DC Load Disconnect

The MM-DCLD (DC Load Disconnect) pigtail adapter is designed to provide a 
means to DISABLE the inverter function when a 12-volt DC signal is removed.

Ignition Switch Activate

The MM-ISA (Ignition Switch Activate) is a pigtail adapter is designed to 
automatically ENABLE the inverter function when a 12-volt DC signal is 
supplied.

Содержание MAGNUM ENERGY MM Series

Страница 1: ...Owner s Manual MM Series Inverters...

Страница 2: ...Due to continuous improvements and product updates the images shown in this manual may not exactly match the unit purchased Restrictions on Use The MM Series inverter may only be used in life support...

Страница 3: ...e inverter if it has been damaged Do not dismantle the inverter there are no user serviceable parts contained in this product Attempting to service the unit yourself could cause electrical shock Inter...

Страница 4: ...ries can produce explosive gasses For compartment or enclosure installations always vent batteries to the outside Provide at least one inch of air space between batteries to provide optimum cooling Ne...

Страница 5: ...6 AC Wiring MM612 MM1212 models 15 2 6 1 Neutral to Safety Ground Bonding 15 2 6 2 AC Wiring Connections 15 2 6 3 AC Wire Size and Overcurrent Protection 16 2 6 4 AC Input Wiring 17 2 6 5 AC Output Wi...

Страница 6: ...ltage Change 23 Figure B 1 Series Battery Wiring 30 Figure B 2 Parallel Battery Wiring 31 Figure B 3 Series Parallel Battery Wiring 31 Figure C 1 Performing an Inverter Reset 33 List of Tables Table 1...

Страница 7: ...a 15 battery temperature sensor MM1212 G a 1200 watt inverter charger with 12 amp AC transfer relay and 70 amp 4 stage PFC charger AC input is provided by a standard 3 ft plug in power cord and the A...

Страница 8: ...nt of power they consume The rating is printed on the product s nameplate label usually located on its chassis near the AC power cord Even though it is difficult to calculate exactly how long an inver...

Страница 9: ...tions on the inverter MM612 MM1212 models only b GFCI Outlet a Ground Fault Circuit Interrupter GFCI outlet with test and reset capability MM1212 G model only 8 Mounting Flanges x4 used to secure the...

Страница 10: ...nding system This terminal accepts CU AL conductors from 14 AWG to 6 AWG 2 1 mm2 to 13 3 mm2 Figure 1 4 Left Side Features Back Side 13 14 1 6 Battery Temperature Sensor MM1212 MM1212 G A plug in exte...

Страница 11: ...nuts installed on the DC terminals Battery Temperature Sensor MM1212 MM1212 G models only MM Series Owner s Manual If items appear to be missing or damaged contact your authorized Magnum Energy deale...

Страница 12: ...re Minimum clearances can be reduced if airflow is increased but in no case should clearance around the inverter be less than 2 5 cm on all sides Safe Keep any flammable combustible material e g paper...

Страница 13: ...anges to reduce vibration Refer to Figure 2 2 for unit dimensions After the inverter has been properly mounted proceed to the DC Wiring section Wall Mounted right side up Shelf Mounted right side up S...

Страница 14: ...ata Technologies 8 Installation Figure 2 3 Basic Installation Diagram MM612 MM1212 AC Main Panel Overcurrent Device Battery Bank AC IN AC Loads DVD TV Tools AC Sub Panel AC Outlet AC OUT DC Ground DC...

Страница 15: ...2016 Sensata Technologies 9 Installation Figure 2 4 Basic Installation Diagram MM1212 G Overcurrent Device Battery Bank AC IN AC Loads AC OUT DC Ground DC Disconnect DVD Tools TV...

Страница 16: ...tional connection will contribute to additional voltage drops and these extra connections points may loosen during use All wiring to the battery terminals should be checked periodically once a month f...

Страница 17: ...though an overcurrent protection device is still required Because the DC disconnect is not required a fuse is usually used as the overcurrent device in these installations These installations also do...

Страница 18: ...using this inverter in a vehicle DO NOT connect the battery negative cable to the vehicle s safety ground Connect it only to the inverter s negative battery terminal If there are any non factory inst...

Страница 19: ...correct DC voltage and polarity have been verified Info For optimum performance a minimum battery bank of 200 AHr is recommended Depending upon the type of batteries you use in the installation 6 or 1...

Страница 20: ...ve terminal of the first battery string to the inverter s negative terminal see Figure B 3 for reference Battery Temperature Sensor MM1212 MM1212 G models only Connect the RJ11 connector end of the BT...

Страница 21: ...le neutral to ground connections Therefore ensure that the inverter does not also connect neutral to ground while the other AC source is powering the inverter loads While inverting the MM Series inver...

Страница 22: ...ected against overcurrent and have a means to disconnect the AC circuits Overcurrent protection must be provided by fuses or circuit breakers and must be properly sized and rated for the wire they are...

Страница 23: ...Series AC wires colored black HOT IN white NEU IN and green AC GROUND respectively 4 After making the AC input connections secure the AC input cable by tightening the strain relief The AC input wiring...

Страница 24: ...ound Fault Circuit Interruption GFCI Breakers If installing this inverter in the wiring system of a mobile application RV marine truck a GFCI may be installed to protect some branch circuits powered b...

Страница 25: ...atus indicator is blinking indicating the inverter is providing AC power 5 Check the output voltage of the inverter by connecting a multimeter to the outlets powered by the inverter Verify the voltage...

Страница 26: ...ing for an AC load i e electrical appliance Whenever an AC load greater than 5 watts is turned on the inverter recognizes the need for power and automatically starts inverting When there is no load or...

Страница 27: ...a battery charger the inverter monitors the AC input for acceptable voltage Once the inverter has accepted the AC input the AC transfer relay will close and charging will begin Once charging the DC vo...

Страница 28: ...ut is continually monitored Whenever AC power falls below the VAC dropout voltage 80 VAC default the inverter automatically transfers back to Inverter mode with minimum interruption to your appliances...

Страница 29: ...l not be compensated and the battery will maintain the charge it had at a temperature of 77 F 25 C The life of the batteries may be reduced if they are subjected to large temperature changes when the...

Страница 30: ...y excessive or unregulated voltage from solar panels or other external charging sources Overload During Inverter and Standby modes the inverter monitors the DC and AC current levels In the event of a...

Страница 31: ...inals Blinks On once every second The inverter is on and is using energy from the battery The inverter is either providing full power to the loads connected to the inverter or it s in Search mode and...

Страница 32: ...available on the MM612 model and is adjusted to 5W wakes up and inverts if loads exceed 5 watts on the MM1212 and MM1212 G models LowBatCutOut This setting determines when the inverter will turn off...

Страница 33: ...nverter ensure cool air is available to pass through the inverter AC Overload status indicator blinks x4 4 secs The inverter has turned off because the connected loads are larger than the inverter s o...

Страница 34: ...rger efficiency maximum NA 88 Power factor NA 0 95 Input current rated output NA 9 AAC Temperature compensation NA Yes with BTS General Features and Capabilities Protection circuitry Low High Battery...

Страница 35: ...items are required depending upon the intended use of the inverter Auto Generator Start Controller The ME AGS N Automatic Generator Start controller Network version is designed to automatically start...

Страница 36: ...est suited for the inverter installation and cost Use only the same battery type for all batteries in the bank For best performance all batteries should be from the same lot and date This information...

Страница 37: ...ercurrent protection 12 volts 100 AHrs 12 volts 100 AHrs 12 volts 100 AHrs 12 volts 100 AHrs to 12 VDC inverter Series Parallel Wiring A series parallel configuration increases both voltage to match t...

Страница 38: ...ne Off Season Storage When placing a coach boat into seasonal storage perform the following to ensure the system is properly shut down or properly configured for seasonal storage This is especially im...

Страница 39: ...all battery power positive and negative to the inverter do not remove the DC negative connections to the inverter or any accessory until all positive battery connections have been disconnected This w...

Отзывы: