background image

GREEN FLASH - Battery is charging in either Boost (steady flash LED) or Refresh mode 

(2x short flash LED)

GREEN - Maintaining battery in Eco-float mode.

RED/YELLOW - Battery is connected backwards. Correct connections and retry.

YELLOW - Charger in initial power-on sequence.

RED - No charger output. Verify battery and source voltage are connected.

GREEN/YELLOW - Overvoltage Protection, charger will return to normal operation once 

externally caused over voltage condition is removed.

OFF - AC source not connected.  Verify source is connected and has proper 

voltage and frequency.

Getting Started

The charger automatically starts in Boost mode at power-on or after a battery discharge. It remains in Boost mode until the 
battery is fully charged. The charger then shifts to Eco-float mode to lengthen battery life. Refresh mode runs periodically to 
insure that the battery remains fully charged. This cycle continues until the next discharge event.  

Operation

 

PATENTED US 9,270,140; 9,385,556; 9,413,186; 9,509,164; 9,948,125

Battery Charger

Need Help? 

CONTACT SENS CUSTOMER SERVICE: 

800-742-2326  /  303-678-7500  /  [email protected]

 3.98 

 6.46 

 5.65 

 1.46 

 4X  .266 

 3.41 

NOTES:

THIS DRAWING IS FOR REFERENCE ONLY.

1.

SUPPLIED WITH 6FT AC CORD WITH NEMA 5-15 PLUG.

2.

SUPPLIED WITH 6FT DC CORD WITH RING TERMINALS. 

3.

D

C

B

A

A

B

C

D

1

2

3

4

5

6

7

8

8

7

6

5

4

3

2

1

DIMENSIONS & TOLERANCES

 PER ASME Y14.5 - 2009

20

B

SENS - MGLE

SHEET 1 OF 1

SENS MICROGENIUS LE OUTLINE DRAWING

8/8/2018

 

 

ERS

REV

DOCUMENT NUMBER

SIZE

DESCRIPTION

NAME

DATE

CHECKED

DRAWN

THIRD ANGLE PROJECTION

UNLESS OTHERWISE SPECIFIED:
DIMENSIONS ARE IN 

INCHES

DEFAULT TOLERANCES:
ANGLES      1  

TWO PLACE DECIMAL      .015

THREE PLACE DECIMAL    .005
DO NOT SCALE DRAWING

THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE 

PROPERTY OF STORED ENERGY SYSTEMS, LLC.  ANY 

REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN 

PERMISSION OF STORED ENERGY SYSTEMS, LLC. IS PROHIBITED.

                          © STORED ENERGY SYSTEMS, LLC

1840 INDUSTRIAL CIRCLE

LONGMONT, CO 80501

303-678-7500

WWW.SENS-USA.COM

Enclosure rated IP67

Mount vertically for optimal 

cooling using #8 - 1/4-20 inch or 

M4 - M6 metric screws

Operating Temp -25C to +70C

•  12V, 6A full spec to +50C 
•  12V, 10A and 24V, 5A full 

spec to +40C

Time 

12.8/25.6V 

0

 

Current accepted 

by battery 

DYNAMIC BOOST 

CHARGE MODE

 

 

HELIX  

ECO-FLOAT 

MODE 

HELIX 

REFRESH 

MODE 

14.5/29.0V 

14.3/28.6V 

Charger determines time in Boost 

charge mode automatically 

~10 hours 

~2 

 hours 

~10 hours 

~2 

 hours 

Vo

lta

ge

 

Cu

rr

ent

 

Mounting

 

LEDs/Troubleshooting

 

GREEN - Battery is charged. Boost cycle complete, charger now in Eco-float.

YELLOW FLASH - Check battery or load. Boost mode time limit expired indicating exces-

sive load, battery capacity is too large or battery has an internal short. 

RED/RED FLASH - Battery bad or disconnected. Battery voltage dropped below preset 

threshold within one hour of boost termination. Verify battery         

connected. Battery unable to hold charge or has an internal short. 

OFF - Battery charging not yet complete. 

Note - battery status updated every 100 seconds

Dimensions in inches