SENKO pellet AIR stoves
–
Instruction manual
13
PELLET
STOVE
We advise you
to check
the following elements
prior to installation:
Appropriate minimum volume of space where the stove will be
installed (avoid placing the stove into hollow or narrow spaces
under 40 m
3
of volume);
Ensure suitable and proper exchange of primary air necessary for
combustion via connection with external air;
Proper execution of chimney and smoke venting pipes.
Prior to installation
it is necessary to
control
proper
positioning
of the
stove and the chimney, which must comply with:
Prohibitions concerning the installation;
Safety distances;
Limitation prescribed by the local administrative regulations or
special safety measures prescribed by the authority;
It is not allowed to install the stove in a room or bathroom
where another heating device without the autonomous air
exchange already exists.
It is forbidden to install the stove in the room with explosive
atmosphere
.
A
500 mm
from the back wall
B
500 mm
from the side wall
C
800 mm
from the front grid
D
500 mm
floor protection
E
300 mm
(measured from the
maximum angle of firebox
door opening )
BACK WALL
S
ID
E
W
A
LL
S
ID
E
W
A
LL
FLOOR PROTECTION
RADIATION AREA
Table 2
Figure 4