background image

www.senjusprinkler.com

Document No. U03688A • 01-06-2022 

Page 1 of 8 

The Model RC-QR Commercial Flat Concealed Sprinklers are automatic sprinklers of the compressed fusible solder type. 
They are decorative and quick responding. The Cover Plate Assembly hides the Deflector, Heat Responsive Element 
etc., which is concealed above the ceiling. The cover plate has a flat profile, and its diameter is extremely small (2-5/8 
inch, 68mm). The push-on and/or thread-on, thread-off design of the concealed cover plate assembly allows for easy 
installation of the cover plate.

Therefore, the Model RC-QR should be your first choice when aesthetics is the major consideration for ultimate appeal 
and unbeatable performance is desired.

They are to be installed per NFPA 13 guidelines.

The Model RC-QR has a 5.6 (80.6 LPM/bar

1/2

) K-factor.

For extended installation flexibility, the Model RC-QR provides 1/2 inch (12.8mm) vertical adjustment. This adjustment in 
installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with 
a range of pipe lengths.

The heat sensitivity and water distribution design of Model RC-QR allows for an increased chance of occupants to escape 
or evacuate in case of a fire. However, fire sprinkler systems are not a substitute for fire safety awareness or fire safety 
construction required by building codes.

G E N E R A L   D E S C R I P T I O N

Commercial Flat Concealed Sprinkler, Pendent 
Quick Response, Standard Coverage

Model RC-QR

K-Factor: 5.6 

 SIN: SS9561

WA R N I N G S

The Model RC-QR must be installed and maintained in accordance with the rules stated herein as well as in compliance 
with the applicable standards of the National Fire Protection Association regulations and the standards of any other 
authorities having jurisdiction.

In the event of this condition, consult the authorities having jurisdiction for guidance and approval. Failure to do so may 
impair the integrity of these devices.

Содержание RC-QR

Страница 1: ...des 1 2 inch 12 8mm vertical adjustment This adjustment in installation decreases the need for precise cutting of the pipe that drops to the sprinkler and allows for a perfect fit with a range of pipe...

Страница 2: ...of this document to the owner or their representative and in turn it is the obligation of the owner to provide a copy of this document to a succeeding owner The owner is responsible for maintaining th...

Страница 3: ...his document may concern specifications which are more stringent and which take precedence over those specified in NFPA 13 or by the authority having jurisdiction The Model RC QR must not be used in a...

Страница 4: ...ected to a corrosive environment including the following 1 Chlorine ion and Chloride environment Stress corrosion cracking may be caused by exposure to environments with Chlorine ion and Chloride Expo...

Страница 5: ...ing has been lifted from its normal position in the process of tightening the Cover Plate Assembly readjust the cover plate assembly as necessary If the flange of the Cover Plate Assembly cannot conta...

Страница 6: ...ective Cap Removal Deflector 5 8 1 4 16 6 4 mm Mounting Surface 2 50 8 mm Cup Screw 2 5 8 68 mm or 3 1 4 83 mm or UL only 2 5 8 square 68 mm 2 50 8 mm Cover Plate Assembly 1 16 1 6 mm Figure 6 Install...

Страница 7: ...r duster or gently vacuuming with a soft bristle i e dusting brush attachment Exercise suitable safety precautions in the use and storage of highly flammable materials The rapid rate of fire developme...

Страница 8: ...ive ratchet not included Socket NR H Plastic for use with a 1 2 drive ratchet not included Cap Removal Tool for RC Cover Plate Installation Tool Sprinkler Model RC QR SIN SS9561 Quick Response Standar...