ModBUS CONNECTION RULES

1) Install the modules in the DIN rail (120 max)

2) Connect the remote modules using cables of an appropriate length. The following table shows cable length data:

- Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables 

that connect the two farthest modules (see Diagram 1).

- Derivation length: maximum length of a derivation 2 m (see Diagram 1).

For maximum performance, it is recommended to use special shielded cables, such as BELDEN 9841.

INSTALLATION REGULATIONS

The  module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life, 

adequate ventilation must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots. 

Avoid mounting modules over heat-generating equipment. Installation in the bottom part of the electrical panel is 

recommended.

Insertion in the DIN rail

As shown in figure:

1.  Insert the IDC10 rear connector of the module on a free slot of 

the DIN rail 

 

(the insertion is univocal since the connectors are polarized).

2.  To secure the module to the DIN rail, tighten the two hooks on 

the side of the IDC10 rear connector.

USB PORT

The module is designed to arrange data according to the modes defined by the MODBUS protocol. It has a micro 

USB connector on the front panel and can be configured using applications and/or software programs. The USB 

communication has priority over the RS485 communication. 

The USB serial port uses the following communication parameters: 

2400,8,N,1

The USB communication port 

responds exactly like the  RS485 port with the exception of the communication parameters. During the use of the 

USB port, the bus will be inactive; it will reactivate automatically a few seconds after the last message exchanged 

on the USB port. EASY SETUP is the software to use for the configuration. For more information, visit www.sene-

ca.it/

products/z203-2

Check that the device in question is included in the list of products supported by the Easy Setup APP in the store.

6/8

CU-A-MICRO-

OTG

CU-A-MICROB

CU-A-MICROB

 

1200 m

2 m

2

1

4

5

Ld

Diagram 1

Bus length

Derivation 

length

Module

Module

Module

Module

Module 3

Bus length

Ld= derivation length

Insertion on

the DIN rail

MODULE

DIN rail

Android APP 

configuration

PC software 

configuration

Содержание Z203-2

Страница 1: ...single phase network analyzer SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and configuration software visit www seneca i...

Страница 2: ...seneca it products z203 2 Important Obstructing ventilation slots with any object is prohibited Installing the module next to devices that generate heat is prohibited Electrical and electronic waste...

Страница 3: ...factor 3 Maximum current 15 A Frequency from 35 to 75 Hz Class Base Prec Voltmeter 0 5 Ammeter 0 5 Wattmeter 0 5 active power ANALOGUE OUTPUT Voltage output 0 10 Vdc 0 5 Vdc minimum load resistance 2...

Страница 4: ...ional to the full scale value of the measured quantity For example if the retransmitted signal is in current 4 20 mA and the quantity to retransmit the voltage Vrms we will have that 4 mA will corresp...

Страница 5: ...BAUD RATE 19200 38400 57600 1 ADDRESS 2 63 From EEPROM 5 8 DIP Switch status SW2 POSITION DESCRIPTION 1 2 3 4 5 6 7 8 Network frequency 50 Hz NETWORK NOMINAL FREQUENCY SELECTION 50 60 Hz Network frequ...

Страница 6: ...nnectors are polarized 2 To secure the module to the DIN rail tighten the two hooks on the side of the IDC10 rear connector USB PORT The module is designed to arrange data according to the modes defin...

Страница 7: ...Connection cable signal protection shield recom mended Retransmitted input output The module accepts an input voltage up to 500 Vac maximum Provide the input voltage to terminals 10 and 12 and connect...

Страница 8: ...tings procedures refer to the USER MANUAL downloadable from www seneca it products z203 2 ATTENTION The upper power supply limits must not be exceeded as this might cause serious damage to the module...

Отзывы: