background image

MODULE LAYOUT

Dimensions LxHxD

 17.5 x 102.5 x 111 mm; 

Weight:

 

130 g; 

Enclosure:

 PA6, black

17.5 mm

111 mm

102.5 mm

PRELIMINARY WARNINGS

The word 

WARNING

 preceded by the symbol            indicates conditions or actions that put the user's safety at 

risk. The word 

ATTENTION

 preceded by the symbol            indicates conditions or actions that might damage the 

instrument or the connected equipment.

The warranty shall become null and void in the event of improper use or tampering with the module or devices 

supplied by the manufacturer as necessary for its correct operation, and if the instructions contained in this manu-

al are not followed.

WARNING

: The full content of this manual must be read before any operation. The module must only be used by 

qualified electricians. Specific documentation is available at www.seneca.it/products/z203-2

Important: Obstructing ventilation slots with any object is prohibited. 

Installing the module next to devices that generate heat is prohibited.

Electrical and electronic waste disposal (applicable in the European Union and other countries with recycling). The 

symbol on the product or its packaging shows the product must be surrendered to a collection centre authorized to 

recycle electrical and electronic waste.

The module must be repaired and damaged parts replaced by the Manufacturer. The product is sensitive to electro-

static discharges. Take appropriate measures during any operation.

LED

STATUS

LED meaning

PWR Green

ON

The device is powered correctly

FAIL yellow

Flashing

Measured voltage lower than 40 Vac and current <20 mA

FAIL yellow

ON

Communication error between internal peripheral devices

RX Red

Flashing

Receipt of packet completed

RX Red

ON

Anomaly / Check connection

TX Red

Flashing

Transmission of packet completed

SIGNALS VIA LED ON FRONT PANEL

2/8

Содержание Z203-2

Страница 1: ...single phase network analyzer SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and configuration software visit www seneca i...

Страница 2: ...seneca it products z203 2 Important Obstructing ventilation slots with any object is prohibited Installing the module next to devices that generate heat is prohibited Electrical and electronic waste...

Страница 3: ...factor 3 Maximum current 15 A Frequency from 35 to 75 Hz Class Base Prec Voltmeter 0 5 Ammeter 0 5 Wattmeter 0 5 active power ANALOGUE OUTPUT Voltage output 0 10 Vdc 0 5 Vdc minimum load resistance 2...

Страница 4: ...ional to the full scale value of the measured quantity For example if the retransmitted signal is in current 4 20 mA and the quantity to retransmit the voltage Vrms we will have that 4 mA will corresp...

Страница 5: ...BAUD RATE 19200 38400 57600 1 ADDRESS 2 63 From EEPROM 5 8 DIP Switch status SW2 POSITION DESCRIPTION 1 2 3 4 5 6 7 8 Network frequency 50 Hz NETWORK NOMINAL FREQUENCY SELECTION 50 60 Hz Network frequ...

Страница 6: ...nnectors are polarized 2 To secure the module to the DIN rail tighten the two hooks on the side of the IDC10 rear connector USB PORT The module is designed to arrange data according to the modes defin...

Страница 7: ...Connection cable signal protection shield recom mended Retransmitted input output The module accepts an input voltage up to 500 Vac maximum Provide the input voltage to terminals 10 and 12 and connect...

Страница 8: ...tings procedures refer to the USER MANUAL downloadable from www seneca it products z203 2 ATTENTION The upper power supply limits must not be exceeded as this might cause serious damage to the module...

Отзывы: