Moving
Average
Filter
Number of samples in the moving
average for weight Measure.
Registers 40064 - 40065 contain the
result of moving average.
Range from 1 to 100.
unsigned
16 bit
R/W Flash
100
40061
60
ADC RAW
Gross
Value
Analogic to digital converter raw value
(Gross weight)
unsigned
16 bit
R RAM
0
40062
61
Integer
RAW Net
Weight
If bipolar, the value is from –31000 (full
traction) to +31000 (full compression)
If unipolar, the value is from 0 (no
compression) to +62000 (full
compression)
Signed 16
bit /
Unsigned
16 bit
R RAM
0
40063
62
Net
Weight
Measure
Value
Net Weight Value
Floating
Point
32 bit
R RAM
0
40064-
40065
63-64
Status
Bit [6]
Z-SG-L MODEL:
0= digital input is low
1= digital input is high
Z-SG MODEL: not used
Bit[5]
Z-SG-L MODEL:
1 =digital output controlled by Modbus (if
unsigned
16 bit
R RAM
0
40066