USER MANUAL – Z-SG
11
BAUD-RATE (Dip-Switches: SW1)
1
2
Meaning
Baud-rate=9600 Baud
Baud-rate=19200 Baud
Baud-rate=38400 Baud
Baud-rate=57600 Baud
ADDRESS (Dip-Switches: SW1)
3
4
5
6
7
8
Meaning
Address and Baud-Rate are acquired from memory(EEPROM)
Address=1
Address=2
Address=3
Address=4
X
X
X
X
X
X
……………………
Address=63
DIGITAL INPUT/OUTPUT (Dip-Switches: SW2)
1
Meaning
Digital input. Calibration button (used during calibration procedure) is enabled
Digital output
ANALOG OUTPUT (Dip-Switches: SW2)
2
3
Meaning
Output scale range=0..10V
Output scale range=0..5V
Output scale range=0..20mA
Output scale range=4..20mA
OPERATING MODE (Dip-Switches: SW2)
4
5
Meaning