ENGLISH - 5/8

t

10 GND
11 A(+)
12 B (-)

10 GND
11 RX
12 TX

N.A.2=22

CO.2=23

N.C.2=24

N.A.1=19

CO.1=20

N.C.1=21

2
1

3

+12V

at 40 mA

C

Auxiliary volt.

Powersupply

Powersupply

19    28V

50 – 60 Hz

A

11    40V

6.5W

C

Warning

powersupply

: The

upper limits must not be exceeded in order to avoid

serious damage to the module.

Power off the module, with the PS1 button, before connecting the inputs and outputs.

In order to satisfy the electromagnetic compliance requirements:
- Use shielded cables for the signals transmission;
- Connect the shield to a preferential ground for devices;
- Space the shielded cables from other cables used for power installations
(transformers, inverters, motors, induction ovens, etc...);

2

POWERSUPPLY

The power supply must be connected to terminals 2 and 3.
The supply voltage must be between:

.

11 and 40V

(any polarity), or between 19 and 28 V

C

A

The power supply source must be protected from any malfunctions
of the module through appropriately sized safety fuse.

2

ANALOG INPUTS

Voltage

Current active sensor (4 fili) Current passive sensor (2 fili) The module has two

software voltage or
current configurable
analog inputs.
For the configuration
software you can read
the user manual.

2

DIGITAL INPUTS

Internal power supply NPN

Internal power supply PNP

External power supply PNP

2

DIGITAL OUTPUTS

The module has two

digital

outputs with free contacts.

The figures show the internal
relay contacts available.

2

COM2 SERIAL PORT

RS485

SERIAL

PORT

(SW2=OFF )

”

RS232

SERIAL

PORT

(SW2=ON )

“

The module has a serial port
available to terminals 10-11-12
You can configure this port
through SW2 switch.

ELECTRICAL CONNECTIONS

5 AI1
6 AI2

’

’

1 12V

12V

40mA

C

4 GND
5 AI1
6 AI2

’

’

+

+

4 GND
5 AI1
6 AI2

+

+

13 DI1

14 DI2

15 +12V

16 GND

17 DI3

18 DI4

0V

C

Max 24V

C

12V

20mA

C

13 DI1

14 DI2

15 +12V

16 GND

17 DI3

18 DI4

13 DI1

14 DI2

15 +12V

16 GND

17 DI3

18 DI4

0V

C

Содержание Z-GPRS3 HW2

Страница 1: ...bed in it This informations may be modified or integrated for technical and or commercial requirements SENECA s r l Headquarters Via Austria 26 35127 PADOVA ITALY Phone 39 049 8705355 8705359 Fax 39 0...

Страница 2: ...V or 19 28 V P max C C 50 60 Hz 6 5W If the voltage is lower than 12 V the internal UPS battery can t be recharged DIGITAL INPUTS Number of channels 4 PNP or NPN configurable Input voltage OFF 4V ON...

Страница 3: ...thout any interruptions for at least 72 hours in order to charge the internal batteries Disposal of electrical electronic equipment applicable throughout the EU and other countries with separate colle...

Страница 4: ...ear IDC10 connector into a free slot of DIN rail accessory as you can see in fig 1a the insertion is one way only because the connectors are polarized 3 To secure the module to the IEC EN 60715 DIN ra...

Страница 5: ...r between 19 and 28 V C A The power supply source must be protected from any malfunctions of the module through appropriately sized safety fuse 2 ANALOG INPUTS Voltage Current active sensor 4 fili Cur...

Страница 6: ...e not used Fast Blinking 0 2s ON 0 2s OFF n o nononononononono RS485 or RS232 communication Timeout GSM Yellow Blinking 64ms ON 3s OFF n o noooooooooooooooooooooooo Connected to the GSM network Blinki...

Страница 7: ...ct 4 PWR STS Green ON n Z GPRS3 ON inactive log status ready Slow Blinking 2 8 sec ON 0 4 sec OFF nnnnnnnnnnnnnnoo Z GPRS3 active log status normal Slow Blinking 1 6 sec ON 1 6 sec OFF nnnnnnnnooooooo...

Страница 8: ...I D 3 I D 2 I DI1 ETH LNK ETH ACT SD PWR ETHERNET ANTENNA Z GPRS3 19 20 21 22 23 24 micro USB micro USB 10 11 12 13 14 15 16 17 18 1 2 3 4 5 6 S SENECA ETH USB GSM 485 ACT DO2 D 1 O The module has a R...