ENGLISH - 2/8
t
STANDARDS
EN61000-6-4
Electromagnetic emission, industrial environment
.
EN61000-6-2
Electromagnetic immunity, industrial environment.
.
EN301 511
Harmonized standard for mobile stations
.
EN301 489-1
ElectroMagnetic Compatibility for radio equipment
.
EN301 489-7
Specific (EMC) conditions for mobile radio equipment
EN60950
Safety of information Technology Equipment.
INSULATION
ENVIRONMENTAL
CONDITIONS
Temperature
Humidity
Storage temperature
Protection rating
0 + 50°C / (-10 + 40°C with internal UPS use).
–
–
30% –
t
ing.
90% no condens
–
–
-20 + 65°C / (-20 + 45°C < 6
with internal UPS use).
months
IP20.
MOUNTING
35mm IEC EN60715 DIN Rail.
INTERNAL UPS
Backup rechargeable batteries, NiMH
CONNECTIONS
Removable
three pole screw terminal pitch 5mm
, for cable up to 2.5 mm ,
2
rear IDC10, front RJ45, Micro USB and Antenna SMA.
POWERSUPPLY
Voltage
Power absorbed
11 – 40 V or 19 – 28 V
–
. P. max
C
C
50 60 Hz
< 6.5W.
If the voltage is lower than 12 V, the internal UPS battery can' t be
recharged.
DIGITAL INPUTS
Number of channels 4. PNP or NPN configurable.
Input voltage OFF<4V ON>8V (Max. 24V ). Input current 20mA.
C
Max. frequency 30Hz. Absorbed Current 3mA @ 12V
10mA @ 24V .
C
C
TOTALIZERS
Four 32 bit totalizers on non-volatile memory.
COUNTERS
Four 32 bit resettable counters on non-volatile memory.
DIGITAL OUTPUTS
Number of channels
SPDT Relays with free contacts.
2.
Max. Voltage 250V . Max. Current 2A.
A
ANALOG INPUTS
Number of channels 2. mA
or V
configurable.
C
C
Voltage input 0 – 30V. accuracy 0.1% of the Full Scale.
Current input 0 20mA
–
accuracy 0.1% of the Full Scale.
Inputs protection 40V / 25mA. Resolution 16 bit.
COMMUNICATION
PORTS
Rear RS485 COM1 port. RS485 or RS232 M10-M11-M12 COM2 screw
terminals port. Ethernet 10/100 baseT RJ45 frontal port with autoswitch.
MicroUSB side port.
TECHNICAL SPECIFICATIONS
Communication
Power
Supply
Input
Output
1500 V
~
3 0 V
00
~
USB
RS485
RS485
RJ45
DI 1
DI 2
DI 3
DI 4
AI 1
AI 2
DO 1
DO 2