INSTALLATION MANUAL

4/4

ELECTRICAL CONNECTIONS

Z-8TC-SI

Z-8TC-SI-LAB

Power supply and Modbus interface are available using the Seneca DIN rail bus, via the IDC10 rear connector, or the Z-PC-DI-

NAL-17.5 accessory.

RS485 GND

 

RS485 A

 

RS485 B

 

Power Supply AC / +

 

Power Supply  AC / -

IDC 10

Back connector (IDC 10)

The illustration shows the meanings of the various IDC10 connector 

pins if signals are to be sent via them directly.

To meet the electromagnetic immunity requirements:

- use shielded signal cables;

- connect the shield to a preferential instrumentation earth system;

- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc.).

INSTALLATION REGULATIONS

MODBUS CONNECTION RULES

The module has been designed for vertical installation on a DIN 46277 rail. For optimal operation and long life, adequate ventila-

tion must be provided. Avoid positioning ducting or other objects that obstruct the ventilation slots. Avoid mounting modules over 

heat-generating equipment. Installation in the bottom part of the electrical panel is recommended.

These are open type devices intended for installation in a final casing/panel that offers mechanical protection and protection 

against the spread of fire.

1) Install the modules in the DIN rail (120 max)

2) Connect the remote modules using cables of an appropriate length. The following table shows cable length data:

-Bus length: maximum length of the Modbus network according to the Baud Rate. This is the length of the cables that connect 

the two farthest modules (see Diagram 1).

-Derivation length: maximum length of a derivation 2 m (see Diagram 1).

Lunghezza 

bus

Lunghezza

derivazione

1200 m

2 m

Schema 1

Modulo 2

Modulo 1

Modulo 3

Modulo 4

Modulo 5

Lunghezza del Bus

Ld= Lunghezza derivazione

Ld

For maximum performance, it is recommended to use special shielded cables manufactured specifically for RS485 communication.

Bus length

Derivation 

length

Module 1

Module 2

Module 5

Module 4

Module 3

Diagram 1

Bus length

Ld= Derivation length

CAUTION

CAUTION

Содержание Z-8TC-SI

Страница 1: ...s during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the module or devices suppli...

Страница 2: ...15200 Baud Micro USB on the front ModBUS protocol 2400 Baud INSULATION COMMUNICATION PORTS RS485 on IDC10 connector PROTOCOL ModBUS RTU TC INPUTS No of channels 8 Type of thermocouples J K E N S R B T L individually activated and configurable in pairs MODULE LAYOUT SIGNALS VIA LED ON FRONT PANEL 17 5 mm Dimensions 17 5 x 102 5 x 111 mm Weight 100 g Container PA6 black 111 mm 102 5 mm LED STATUS LE...

Страница 3: ...1 stop bit FACTORY SETTINGS 1 2 3 4 5 6 7 8 KEY ON OFF SPAN mV 150mV IMPEDANCE 4MΩ ADC 24 bit TEMPERATURE DRIFT 100ppm K COLD JUNCTION ERROR 1 C TEST CURRENT 100nA CMRR 70dB 100ms DMRR 60 dB SUPPORTED INPUT SPECIFICATIONS SENSOR ACCURACY AT 23 C SOLUTION MEASURING RANGE STANDARD J 0 03 0 2 C 0 5µV 0 01 C 0 C 210 1200 C EN 60584 1 1997 K 0 03 0 2 C 0 5µV 0 02 C 0 C 200 1372 C EN 60584 1 1997 R 0 03...

Страница 4: ...bjects that obstruct the ventilation slots Avoid mounting modules over heat generating equipment Installation in the bottom part of the electrical panel is recommended These are open type devices intended for installation in a final casing panel that offers mechanical protection and protection against the spread of fire 1 Install the modules in the DIN rail 120 max 2 Connect the remote modules usi...

Отзывы: