MI00597-0-EN

INSTALLATION MANUAL

3/4

SETTING THE DIP-SWITCHES

The position of the DIP-switches defines the Modbus communication parameters of the module: Address and Baud Rate The fol-

lowing table shows the values of the Baud Rate and the Address according to the setting of the DIP-switches:

Note:

 

When DIP - switches 1 to 8 are OFF, the communication settings are taken from programming (EEPROM).

Note 2

: The RS485 line must be terminated only at the ends of the communication line.

DIP-Switch status

SW1 POSITION

BAUD 

RATE

SW1 POSITION

ADDRESS

POSITION

FUNCTION

1  2  3  4  5  6  7  8  

3  4  5  6  7  8 

9

BOOTLOADER

9600

#1

Enabled

19200

#2

Disabled

38400

#...

10

TERMINATOR

57600

#63

Enabled

From 

EEPROM

From 

EEPROM

Disabled

The position of the dip-switches defines the communication parameters of the module. 

The default configuration is as follows: Address 1, 38400, no parity, 1 stop bit.

FACTORY SETTINGS

1

2

3

4

5

6

7

8

KEY

ON

OFF

SPAN mV

±150mV.

IMPEDANCE

> 4MΩ.

ADC

24 bit.

TEMPERATURE DRIFT

< 100ppm/K.

COLD JUNCTION ERROR

<1°C.

TEST CURRENT

<100nA.

CMRR

70dB @ 100ms

DMRR

60 dB.

SUPPORTED INPUT SPECIFICATIONS

SENSOR

ACCURACY (AT 23°C)

SOLUTION

MEASURING RANGE

STANDARD

J

± (0.03% + 0.2°C) (**)

0.5µV (~0.01°C @ 0°C) 

-210 ÷ +1200°C

EN 60584-1:1997

K

± (0.03% + 0.2°C) (**)

0.5µV (~0.02°C @ 0°C)

-200 ÷ +1372°C

EN 60584-1:1997

R

± (0.03% + 0.3°C) (**)

0.5µV (~0.1°C @ 0°C)

-50 ÷ +1768°C

EN 60584-1:1997

S

± (0.03% + 0.3°C) (**)

0.5µV (~0.1°C @ 0°C)

-50 ÷ +1768°C

EN 60584-1:1997

T

± (0.03% + 0.1°C) (**)

0.5µV (~0.01°C @ 0°C)

-200 ÷ +400°C

EN 60584-1:1997

B

± (0.03% + 0.3°C) (**)

0.5µV (~0.2°C @ 0°C)

+250 ÷ +1820°C (*)

EN 60584-1:1997

E

± (0.03% + 0.2°C) (**)

0.5µV (~0.01°C @ 0°C)

-200 ÷ +1000°C

EN 60584-1:1997

N

± (0.03% + 0.2°C) (**)

0.5µV (~0.02°C @ 0°C)

-200 ÷ +1300°C

EN 60584-1:1997

L

± (0.03% + 0.15°C) (**)

0.5µV (~0.01°C @ 0°C)

-200 ÷ +800°C

Gost 8.585-2001

mV

0.03% + 15µV

0.5µV

± 150 mV

(*) Up to 250°C a zero temperature value is assumed.

(**) Acquisition speed 100ms, no cold junction compensation.

CAUTION

Even at constant room temperature, the declared accuracies are achieved after at least 30 minutes from switching on the device.

Содержание Z-8TC-SI

Страница 1: ...s during any operation PRELIMINARY WARNINGS The word WARNING preceded by the symbol indicates conditions or actions that put the user s safety at risk The word ATTENTION preceded by the symbol indicates conditions or actions that might damage the instrument or the connected equipment The warranty shall become null and void in the event of improper use or tampering with the module or devices suppli...

Страница 2: ...15200 Baud Micro USB on the front ModBUS protocol 2400 Baud INSULATION COMMUNICATION PORTS RS485 on IDC10 connector PROTOCOL ModBUS RTU TC INPUTS No of channels 8 Type of thermocouples J K E N S R B T L individually activated and configurable in pairs MODULE LAYOUT SIGNALS VIA LED ON FRONT PANEL 17 5 mm Dimensions 17 5 x 102 5 x 111 mm Weight 100 g Container PA6 black 111 mm 102 5 mm LED STATUS LE...

Страница 3: ...1 stop bit FACTORY SETTINGS 1 2 3 4 5 6 7 8 KEY ON OFF SPAN mV 150mV IMPEDANCE 4MΩ ADC 24 bit TEMPERATURE DRIFT 100ppm K COLD JUNCTION ERROR 1 C TEST CURRENT 100nA CMRR 70dB 100ms DMRR 60 dB SUPPORTED INPUT SPECIFICATIONS SENSOR ACCURACY AT 23 C SOLUTION MEASURING RANGE STANDARD J 0 03 0 2 C 0 5µV 0 01 C 0 C 210 1200 C EN 60584 1 1997 K 0 03 0 2 C 0 5µV 0 02 C 0 C 200 1372 C EN 60584 1 1997 R 0 03...

Страница 4: ...bjects that obstruct the ventilation slots Avoid mounting modules over heat generating equipment Installation in the bottom part of the electrical panel is recommended These are open type devices intended for installation in a final casing panel that offers mechanical protection and protection against the spread of fire 1 Install the modules in the DIN rail 120 max 2 Connect the remote modules usi...

Отзывы: