ENGLISH
- 6/8
Power supply
Power supply
19 – 28V
50 – 60 Hz
10 – 40V
0.6 W Max
IDC10
POWER SUPPLY
Connect the IDC10 rear connector to provide power supply to module.
The supply voltage must be between:
10 and 40V
(any polarity), or between 19 and 28 V
.
The upper limits mus not be exceeded as this can seriously damage the
module
If the power supply source is not protected against overload, a safety
.
fuse of max. 2.5 A must be installed in the power supply line near the device.
USB
The module has a micro USB port on frontal panel for configuration and MODBUS-RTU parameters
communication.
ELECTRICAL CONNECTIONS
RS485
A
RS485
B
RS485
GND
IDC10
Power supply
AC-
Power supply
AC+
Fig. 4
B
A
Fig. 3
DIP
switch
Slot
Don’t force the insertion
of the IDC10 connector into the Z-PC-DIN bus.
The rear IDC10 connector of the module will be inserted on a free slot of Z-PC-DIN accessory.
In the figure you can see the meaning of the various pins of the rear IDC10 connector if you want to
provide the signals directly through this connector. The pictures
Pic.3
and
Pic.4
show how to
connect powersupply and RS485 COM1 port to the rear IDC10 connector.
In case of Z-PC-DINAL2-17,5 accessory use, the signals may be provided by terminal blocks.
The figure shows the meaning of terminals and the position of DIP-switch (present on each DIN rail
supports) for network termination (not used in case of Modbus network).
GNDSHLD: Shield to protect the signal inside the connection cables from electromagnetic
disturbances (recommended).
USE OF Z-PC-DINAL ACCESSORY
Module 2
Module 3
Module 1
Module 5
Module 4
DL
Terminator
Terminator
Bus Length
DL: Derivation Length
MODBUS
Bus length
Derivation Length
Baudrate
1200 m
2 m
115 kbps
In order to obtain maximum performances it’s
recommended to use a specific shielded cable, as
an example BELDEN 9841.
MODBUS CONNECTION STANDARDS
MI00488
-1