For any variation of the parameters are available in the download area of the website:
www.seneca.it Z-NET and EASY-Z-PC communication software.
For more information about the list of registers and their functions, see the USER manual.
Technical support
Product Informations
CONTACTS
2
DIP-SWITCHES
Before setting the DIP switches, in order to avoid damage to the module, you must disconnect
the power supply.
The DIP-switches position defines the Modbus Address and Baud Rate
communication parameters. In the following table the Baud Rate and Address values are listed as a
function of the DIP-switches position:
SW1
BAUD RATE
SW1
ADDRESS
SW1
TERMINATOR
1 2
3 4 5 6 7 8
9 10
ÈÈ
9600
ÈÈÈÈÈÇ
# 1
x
È
DISABLED
ÈÇ
19200
ÈÈÈÈÇÈ
# 2
x
Ç
ENABLED
ÇÈ
38400
. . . . . . . . .
#. .
1
Ç
ON
ÇÇ
57600
ÇÇÇÇÇÇ
# 63
ÈÈ
FROM
EEPROM
ÈÈÈÈÈÈ
FROM
EEPROM
0
È
OFF
x
Not Used
Note
: If switches from 1 to 8 are in OFF position, communication settings are retrieved from EEPROM.
2nd Note:
The termination of the RS485 line must be carried out only at the ends of the
communication line.
CONFIGURATIONS
2
DEFAULT CONDITION FOR THE CONFIGURATION PARAMETERS OF THE MODULE:
All DIP-switches at OFF position
È
RS485 MODBUS protocol comunication parameters:
38400 8,N,1 Addr. 1
FACTORY SETTINGS
ENGLISH 8 8
- /
MI004950-E