ENGLISH

- 7/8

MI004950-E

t

ELECTRICAL CONNECTION

Sensors REED, PROXIMITY PNP, NPN,
contact, can be connected to the input
terminals. The power supply to these
sensors can be obtained directly from the Z-
D-IO Module (factory configuration),or it can
be externally supplied.

1

7

4

10

2

8

5

11

3

9

6

12

IN1

IN2

IN3

IN4

IN5

0V

1

7

4

10

2

8

5

11

3

9

6

12

IN1

IN2

IN3

IN4

IN5

NO1

NC1

J1 J2

S

1

W

NO2

NC2

NO1

NC1

J1 J2

NO2

NC2

NORMALLY OPEN

NO1

NC1

J1 J2

NO2

NC2

NORMALLY CLOSE

INTERNAL POWER SUPPLY, PNP CONNECTION, NPN CONNECTION

DIGITAL OUTPUT

The relay outputs can be configured to use
the NO contact (factory configuration), or the
NC contact. To modify the output
configuration it is necessary move the J1
and J2 jumper.

Load

Load

Dout1

Dout2

Common

10

11

12

Z-5DI-2DO

The

configuration software, allows the parameter setting.

EASY SETUP

This software is available for free on the Internet site: www.seneca.com.
Some parameters can also be set using

DIP-switches.

CONFIGURATIONS

Detailed information about the list of MODBUS registers and their functions can be found within
the

.

USER MANUAL

MODBUS REGISTERS

+16V

0V

+16V

Содержание Z-5DI-2DO

Страница 1: ...RIGINAL VERSION IS IN ITALIAN LANGUAGE This document is property of SENECA rl Duplication and reproduction are forbidden if not authorized S Contents of the present documentation refers to products and technologies described in it This informations may be modified or integrated for technical and or commercial requirements INSTALLATION MANUAL Z 5DI 2DO Module 5 digital inputs 2 relay outputs modbus...

Страница 2: ...ternal NPN or PNO selectable by software Insulation of the 1500 Vac inputs complying with respect to the remaining low voltage circuits 2 SPST relay outputs with common contact capacity of 250 Vac 2 AAC1 3 kVac insulation between the outputs and the remaining low voltage circuits Inputs with 32 bit totalizers Measure of the period frequency TON TOFF Possibility to set the totalizers for counting f...

Страница 3: ...0 11 4 5 6 Digital Input 3000 VA 1500 VA 1 7 8 9 STANDARDS EN61000 6 4 Electromagnetic emission industrial environment Electromagnetic immunity industrial environment EN61000 6 2 Safety EN61010 1 INSULATION ENVIRONMENTAL COND Temp ratur e e Hu y midit Altitude S rage temperature to P ction degree rote 20 70 C 30 t condensing 90 no Up to 2000 m a s l 20 85 C 20 IP MOUNTING IEC EN 60715 Rail CONNECT...

Страница 4: ...o electrostatic discharge take appropriate countermeasures duringanyoperation No warranty is granted in connection with faults resulting from improper use from modifications or repairs carried out by Manufacturer unauthorized personnel on the device or if the content of this user Manual is not followed It is forbidden to place anything that could obstruct the ventilation slits It is forbidden to i...

Страница 5: ...L In order to ensure optimum performance and a longest working life the module s must be provided with adequate ventilation and no raceways or other objects that obstruct the ventilation slots Never install the modules near heat sources We recommend installation in the lower part of the control panel INSTALLATION RULES Module 2 Module 3 Module 1 Module 5 Module 4 DL Terminator Terminator Bus Lengt...

Страница 6: ...10 Power supply AC Power supply AC Pic 4 B A Pic 3 DIP switch Slot Don t turn upside down don t force the insertion the module and o into f the IDC10 connector the Z PC DIN bus The IDC10 connector located on the rear of the module will be inserted on a free slot of Z PC DIN accessory In the figure you can see the meaning of the various pins of the rear IDC10 connector if you want to provide the si...

Страница 7: ...ORMALLY CLOSE INTERNAL POWER SUPPLY PNP CONNECTION NPN CONNECTION DIGITAL OUTPUT The relay outputs can be configured to use the NO contact factory configuration or the NC contact To modify the output configuration it is necessary move the J1 and J2 jumper Load Load Dout1 Dout2 Common 10 11 12 Z 5DI 2DO The configuration software allows the parameter setting EASY SETUP This software is available fo...

Страница 8: ...table the Baud Rate and Address values are listed as a function of the DIP switches position SW1 BAUD RATE SW1 ADDRESS SW1 TERMINATOR 1 2 3 4 5 6 7 8 9 10 ÈÈ 9600 È È È È È Ç 1 x È DISABLED ÈÇ 19200 È È È È Ç È 2 x Ç ENABLED ÇÈ 38400 1Ç ON ÇÇ 57600 Ç Ç Ç Ç Ç Ç 63 ÈÈ FROM EEPROM È È È È È È FROM EEPROM 0È OFF x Not Used Note If switches from 1 to 8 are in OFF position communication settings are ret...

Отзывы: