USER MANUAL – Z-4AI 

 
 

 

 

3

 

 

 

 

                             

 

POWER SUPPLY 

Supply voltage 

10 

– 40 Vdc or 19 – 28 Vac ( 50Hz - 60Hz) 

Power  
consumption

 

Min: 0.5W;  Max: 2W (to power 4 current loop) 

 

The  power  supply  transformer  necessary  to  supply  the  module  must  comply  with  EN60742 
(Isolated transformers and safety transformers requirements). To protect the power supply, it is 
recommended to install a fuse. 

 

Input connections 

It is possible to connect two types of sensors to the Z-4AI module: 

 

passive sensors

, indicated with “S” label (these sensors have to be supplied: by a module 

external voltage Vext or by the module internal voltage Vaux); 

 

active  sensors

,  indicated  with  “voltage  generator”  or  “current  generator”  label  (these 

sensors have already been supplied). 

In the following figure are shown five possible sensor connections. 

Содержание Z-4AI

Страница 1: ...duction of its are forbidden though partial if not authorized Contents of present documentation refers to products and technologies described in it Though we strive for reach perfection continually all technical data contained in this document may be modified or added due to technical and commercial needs it s impossible eliminate mismatches and discordances completely Contents of present document...

Страница 2: ... sign If Electrical End Scale E E S 2V resolution 60µV se 2V E E S 10V resolution 300µV Sampling time Configurable between 120 ms or 60 ms Accuracy Initial 0 1 of E E S If E E S 2V accuracy 2mV if 2V E E S 10V accuracy 10mV Linearity 0 03 of E E S see initial accuracy Zero 0 05 of E E S see initial accuracy Thermal stability 100 ppm K EMI 1 Protection 30Vdc and 25mA Voltage type IN Bipolar with E ...

Страница 3: ...nts To protect the power supply it is recommended to install a fuse Input connections It is possible to connect two types of sensors to the Z 4AI module passive sensors indicated with S label these sensors have to be supplied by a module external voltage Vext or by the module internal voltage Vaux active sensors indicated with voltage generator or current generator label these sensors have already...

Страница 4: ... Current type 4 sensors as current generator 2 wire D Current active type 4 passive sensors 2 wire Vaux E Current passive type 4 passive sensors 2 wire Vext connect to GND A and D connections are possible only if the absorbed currents sum from all sensors 90mA Dip switches table In the following tables box without circle means Dip Switch 0 OFF state box with circle means Dip Switch 1 ON state ...

Страница 5: ...d INPUT TYPE Dip Switches ANALOG INPUTS 1 2 3 4 5 6 7 8 Meaning IN 1 voltage IN 1 current IN 2 voltage IN 2 current IN 3 voltage IN 3 current IN 4 voltage IN 4 current Name Range Interpretation of register R W Default Address MachineID MSB LSB R 40001 Id_Code Module ID 0x07 Bit 15 8 Ext_Rev Module version Bit 7 0 FWREV Word R 40035 Firmware Code Status Bit R W 40016 Input 4 underflow 0 there isn t...

Страница 6: ... W 40002 Baud rate for RS485 baud rate of module node if parameters are configurated by memory modality 0 4800 1 9600 2 19200 3 38400 4 57600 5 115200 6 1200 7 2400 38400 Bit 15 8 Address for RS485 address of module if parameters are configurated by memory modality from 0x01 1 to 0xFF 255 1 Bit 7 0 INType Bit R W 40025 These bits aren t used Bit 15 4 Input 4 type 0 voltage 1 current 0 Bit 3 Input ...

Страница 7: ...d to input 3 signal 0 deactivated 1 filtering min value 6 filtering max value IN 3 ESS 10000 mV if voltage 20000 µA if current Word R W 40014 Electrical Start Scale E S S of input 3 mV or µA 0 mV IN 3 EES 10000 mV if voltage 20000 µA if current Word R W 40010 Electrical End Scale E E S of input 3 mV or µA 10000 mV IN 3 NSS 32000 Word R W 40032 Normalized Start Scale N S S of input 3 0 IN 3 NES 320...

Страница 8: ... of the errors described in RS485 Registers table RX Constant light Verify if the bus connection is corrected Blinking light The module received a data packet TX Blinking light The module sent a data packet Easy SETUP To configure the Seneca Z PC Line modules it is possible to use Easy SETUP software Free downloadable from the www seneca it the configuration can be performed by RS232 or RS485 bus ...

Отзывы: