USER MANUAL – Z-4AI
7
INPUT 2
IN 2
Between: IN 2-NSS, IN 2-
NES
(if
bit
40003.0=0);
unchangeable
between:
0,10000 (if bit40003.0=1)
Word
R
40018
Normalized measure of input 2
IN2-FILTER
Between: 0, 6
Word
R/W
40005
Filter applied to input 2 signal: 0=deactivated; 1=filtering
min-value; 6=filtering max-value
/
IN 2-ESS
±10000 [mV] (if voltage),
±20000 [µA] (if current)
Word
R/W
40013
Electrical Start Scale (E.S.S.) of input 2 [mV or µA]
0 [mV]
IN 2-EES
±10000 [mV] (if voltage),
±20000 [µA] (if current)
Word
R/W
40009
Electrical End Scale (E.E.S.) of input 2 [mV or µA]
10000
[mV]
IN 2-NSS
±32000
Word
R/W
40031
Normalized Start Scale (N.S.S.) of input 2
0
IN 2-NES
±32000
Word
R/W
40027
Normalized End Scale (N.E.S.) of input 2
10000
INPUT 3
IN 3
Between: IN 3-NSS, IN 3-
NES
(if
bit
40003.0=0);
unchangeable
between:
0,10000 (if bit40003.0=1)
Word
R
40019
Normalized measure of input 3
IN3-FILTER
Between: 0, 6
Word
R/W
40006
Filter applied to input 3 signal: 0=deactivated; 1=filtering
min-value; 6=filtering max-value
/
IN 3-ESS
±10000 [mV] (if voltage),
±20000 [µA] (if current)
Word
R/W
40014
Electrical Start Scale (E.S.S.) of input 3 [mV or µA]
0 [mV]
IN 3-EES
±10000 [mV] (if voltage),
±20000 [µA] (if current)
Word
R/W
40010
Electrical End Scale (E.E.S.) of input 3 [mV or µA]
10000
[mV]
IN 3-NSS
±32000
Word
R/W
40032
Normalized Start Scale (N.S.S.) of input 3
0
IN 3-NES
±32000
Word
R/W
40028
Normalized End Scale (N.E.S.) of input 3
10000
INPUT 4
IN 4
Between: IN 4-NSS, IN 4-
NES
(if
bit
40003.0=0);
unchangeable
between:
0,10000 (if bit40003.0=1)
Word
R
40020
Normalized measure of input 4
IN4-FILTER
Between: 0, 6
Word
R/W
40007
Filter applied to input 4 signal: 0=deactivated; 1=filtering
min-value; 6=filtering max-value
/
IN 4-ESS
±10000 [mV] (if voltage),
±20000 [µA] (if current)
Word
R/W
40015
Electrical Start Scale (E.S.S.) of input 4 [mV or µA]
0 [mV]
IN 4-EES
±10000 [mV] (if voltage),
±20000 [µA] (if current)
Word
R/W
40011
Electrical End Scale (E.E.S.) of input 4 [mV or µA]
10000
[mV]
IN 4-NSS
±32000
Word
R/W
40033
Normalized Start Scale (N.S.S.) of input 4
0
IN 4-NES
±32000
Word
R/W
40029