background image

EasyBuilder Pro Software Settings 

Launch EasyBuilder Pro software, select your project file, 
press F7 shortcut key to open the download dialog box:   
Select Ethernet > IP tab > Enter your HMI IP > Click 
Download to download this project file to HMI. 

( Please refer to EasyBuilder Pro User Manual 
  for software operation details ) 

Communication Connections 

Con.B:   

    Con.A: 

COM1/3 [RS232] 9 Pin, Male, D-sub 

    COM2/3 [RS485] / CAN Bus 9 Pin, Female, D-sub 

Calibration Mode 

To enter touch screen calibration mode, press and hold anywhere on the screen for more than 2 
seconds when HMI starts. 

PIN# 

COM1 [RS232] 

COM3 [RS232] 
(MT8092XE only) 

RxD

 

TxD

 

GND

 

RTS

 

TxD

 

CTS

 

RxD

 

PIN# 

COM2 [RS485] 

COM3 

[RS485] 

CAN 

Bus 

2W 

4W 

Data- 

Rx- 

Data+ 

Rx+ 

Tx- 

Tx+ 

GND 

Data- 

CAN_L 

CAN_H 

Data+ 

*CAN Bus is not applicable for MT8090XE1 model.

NOTE: 

1.

COM2 and COM3 [RS485] 2W support MPI 187.5K, please use one at one time.

2.

COM1 RS-232 RTS/CTS and COM3 RS-232 cannot be used simultaneously.

Limited Warranty 

This product is limited warranted against defects in design and manufacture. 

The proven defective product will either be repaired or replaced, at 

SENECA

’s

discretion. This warranty shall not cover any product which is  

(a) Out of warranty period which is 12 months from the manufacturing month of the HMI products.
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.
(c) Product has been repaired or taken apart by unauthorized technicians.
(d) Products whose identification markings have been removed or damaged.

Power 

The unit can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with 

most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a 

switching power supply. The peak starting current can be as high as 2A.

 

Fusing 
Require- 
ments 

If the display does not come on within 5 seconds of power up, remove power. An internal fuse will 

prevent damage if the polarity of the DC power is incorrect. Check wiring for proper connections 

and try to power up again. 

High 
Voltage 

An Internal fuse will prevent damage for overcurrent 

condition however it isn’t guaranteed. DC 

voltage sources should provide proper isolation from main AC power and similar hazards. 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using 

HMI

 to comply with ICS 

Safety Recommendations. 

Supply 
Voltage 
Condition 

Do not power the unit and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the unit. 

Wire 
Routing 

a. Power wire length should be minimized (Max: 500m shielded, 300m unshielded).

b. Please use twisted pair cables for power wire and signal wire and conform to the impedance

matching.

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices.

d. Keep AC, high energy, and rapidly switching DC power wiring separated from signal wires.

e. Add a resistor and capacitor in the parallel connection between the ungrounded DC power 

supply and the frame ground. This provides a path for static and high frequency dissipation. 

Typical values to use are 1M Ohm and 4700pF.

CAUTION 

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

Hardware 
Considerations 

The system designer should be aware that devices in Controller systems could fail and thereby 

create an unsafe condition. Furthermore, electrical interference in an operator interface can lead to 

equipment start-up, which could result in property damage and/or physical injury to the operator. 

If you use any programmable control systems that require an operator, be aware that this potential 

safety hazard exists and take appropriate precautions. Although the specific design steps depend on 

your particular application, the following precautions generally apply to installation of solid-state 

programmable control devices, and conform to the guidelines for installation of Controllers 

recommended in NEMA ICS 3-304 Control Standards.

 

Programming 
Considerations 

To conform with ICS Safety Recommendations, checks should be placed in the controller to ensure 

that all writable registers that control critical parts of plant or machinery have limit checks built into 

the program, with an out-of-limit safe shut down procedure to ensure safety of personnel. 

DANGER 

Отзывы: