background image

MI00531-2-EN

INSTALLATION MANUAL

4/7

ELECTRICAL CONNECTIONS

The upper power supply limits must not be exceeded, as this could cause serious damage to the module.

Switch the module off before connecting inputs and outputs.

To meet the electromagnetic immunity requirements:

- use shielded signal cables;

- connect the shield to a preferential instrumentation earth system;

- separate shielded cables from other cables used for power installations (transformers, inverters, motors, etc...).

CAUTION

21

22

20

–/

+ /

23 B(-)
24 A(+)
25 GND

POWER SUPPLY

RS485 SERIAL PORT

Connection to the RS485 port.

Polarity is not standardised 

and in some devices may be 

inverted.

ANALOGUE INPUTS: 

The device has 8 analogue inputs that can be configured via DIP-SDWITCH:

CURRENT

 (mA)

Transmitter active

VOLTAGE

 (V) ±30V

THERMOCOUPLE

 (Tc / mV)

B

A

C

+

mA

(40, 43,...60, 63)

CURRENT

 (mA) 

Passive transmitter, 

with external power supply

DIGITAL INPUTS

 (PNP)

With internal power

DIGITAL INPUTS

 (PNP)

With external power

DIGITAL OUTPUTS

 (PNP)

With external power

The relative dip-switch goes to the 

ON position

The relative dip-switch goes to the 

OFF position

The relative dip-switch goes to the 

OFF position

The relative dip-switch goes to the 

ON position

B

A( 40, 43,...60, 63)

C

+

TC/mV

B

A

C

+

(40, 43,...60, 63)

V

.......

B

A

C

S

mA

+

(40, 43, 46, 49)

ALIM.

EXT.

+

The digital outputs must be powered 

externally to function properly.

10

11

12

....

17

18

19

+

52 

53

10

11

12

....

17

18

19

LOAD
LOAD
LOAD

LOAD

LOAD

10

11

12

....

17

18

19

+

Содержание R-8AI-8DIDO

Страница 1: ...ny operation The module must only be used by qualified electricians Specific documentation is available using the QR CODE shown on page 1 Electrical and electronic waste disposal applicable in the Eur...

Страница 2: ...s set Flashing Waiting for the IP address from the DHCP COM R 8AI 8DIDO P version only On Verification of RS485 connection Flashing Data packet transmission over RS485 FAIL On Digital output in FAIL O...

Страница 3: ...IDO version only 2 Ethernet with LAN fault bypass function 100 base T on RJ45 1 RS485 port on terminals R 8AI 8DIDO version only AUXILIARY VOLTAGE OUTPUT Max voltage current 12 Vdc 20 mA DIGITAL INPUT...

Страница 4: ...ome devices may be inverted ANALOGUE INPUTS The device has 8 analogue inputs that can be configured via DIP SDWITCH CURRENT mA Transmitter active VOLTAGE V 30V THERMOCOUPLE Tc mV B A C mA 40 43 60 63...

Страница 5: ...ERA ISOTERMA RAME RAME RAME TC TC ANALOGUE INPUTS Range Resolution Impedance Precision Temperature drift Ext current Voltage V 30 30 Vdc 1 mV 200 kohm 0 1 f s 100 ppm Voltage mV 120 120 mV 4 uV 10 Moh...

Страница 6: ...vice have the following functions DIP SWITCH positions DIP SWITCH SW1 AND SW2 ANALOGUE INPUT OUTPUT CONFIGURATION SW3 DIP SWITCH DEFAULT SETTINGS SETTING THE DIP SWITCHES SW1 SW2 1 2 3 4 1 2 3 4 AI1 A...

Страница 7: ...s not interrupted and the devices downstream of the switched off one will still be accessible This function has a limited duration the connection remains active for a few days typically 4 The fault by...

Отзывы: