INSTALLATION MANUAL

7/7

DAISY-CHAIN ETHERNET CONNECTION

CAUTION

IT IS NOT ALLOWED TO CREATE LOOPS WITH ETHERNET CABLES

Using the daisy-chain connection it is not necessary to use switches to connect the devices.

The following examples show the correct connections.

There must be no loops in the Ethernet cabling, otherwise the communication will not work. The modules and switches 

must be connected eliminating any loops. The following examples show the incorrect connections.

The LAN fault-bypass function allows you to keep the connection between the two Ethernet ports of the device ON, in the 

event of a power failure. If a device turns off, the chain is not interrupted and the devices downstream of the switched-off 

one will still be accessible. This function has a limited duration: the connection remains active for a few days, typically 4. 

The fault-bypass function requires that the sum of the lengths of the two cables connected to the switched off module is less 

than 100m.

MODULE 1

MODULE 2

MODULE 3

MODULE 1

MODULE 2

MODULE 3

MODULE 1

MODULE 2

LOOP

MODULE 3

MODULE 1

LOOP

ETHERNET CONNECTION RULES

For the Ethernet cabling between the devices, the use of the unshielded CAT5 or CAT5e cable is required.

FACTORY IP ADDRESS

The default module IP address is static: 192. 168. 90. 101

WEB SERVER

To access the maintenance Web Server with the 192.168.90.101 factory IP address 

(Default user: admin; Default password: admin) http://192.168.90.101

CAUTION

DO NOT USE DEVICES WITH THE SAME IP ADDRESS IN THE SAME ETHERNET NETWORK.

Содержание R-8AI-8DIDO

Страница 1: ...ny operation The module must only be used by qualified electricians Specific documentation is available using the QR CODE shown on page 1 Electrical and electronic waste disposal applicable in the Eur...

Страница 2: ...s set Flashing Waiting for the IP address from the DHCP COM R 8AI 8DIDO P version only On Verification of RS485 connection Flashing Data packet transmission over RS485 FAIL On Digital output in FAIL O...

Страница 3: ...IDO version only 2 Ethernet with LAN fault bypass function 100 base T on RJ45 1 RS485 port on terminals R 8AI 8DIDO version only AUXILIARY VOLTAGE OUTPUT Max voltage current 12 Vdc 20 mA DIGITAL INPUT...

Страница 4: ...ome devices may be inverted ANALOGUE INPUTS The device has 8 analogue inputs that can be configured via DIP SDWITCH CURRENT mA Transmitter active VOLTAGE V 30V THERMOCOUPLE Tc mV B A C mA 40 43 60 63...

Страница 5: ...ERA ISOTERMA RAME RAME RAME TC TC ANALOGUE INPUTS Range Resolution Impedance Precision Temperature drift Ext current Voltage V 30 30 Vdc 1 mV 200 kohm 0 1 f s 100 ppm Voltage mV 120 120 mV 4 uV 10 Moh...

Страница 6: ...vice have the following functions DIP SWITCH positions DIP SWITCH SW1 AND SW2 ANALOGUE INPUT OUTPUT CONFIGURATION SW3 DIP SWITCH DEFAULT SETTINGS SETTING THE DIP SWITCHES SW1 SW2 1 2 3 4 1 2 3 4 AI1 A...

Страница 7: ...s not interrupted and the devices downstream of the switched off one will still be accessible This function has a limited duration the connection remains active for a few days typically 4 The fault by...

Отзывы: