English 23
P2 group – additional settings (parameters)
No. Description
Range
P2.1
MASTER ROOM UNIT
This setting determines whether the room unit is the
master unit.
In setting 1, the basic settings (desired tempera
-
tures, switchover switch, etc.) are transmitted to oth
-
er slave units. In setting 2, commands for additional
functions (Party, Eco, and Holiday) are transmitted
in addition to the basic settings. In setting 3, only
additional functions are transmitted.
0 – not master unit
1 – master unit (basic
settings)
2 – master unit (basic
settings and additional
functions)
3 – master unit (additional
functions)
P2.2
OPERATION MODE
This setting determines the operation mode of the
zones affected by the room unit.
1 – hysteresis
2 – P
3 – PI
P2.3
ED TIME CONSTANT
This setting determines the ED time constant for P
and PI room temperature control.
10–50min (
20
)
P2.4
THERMOSTAT HYSTERESIS
This setting determines the hysteresis for the
thermostat operation.
0.2–10.0°C (
0.2
)
P2.10
ACTIVATION OF AIR QUALITY/POLLUTION
MEASUREMENT *
This setting activates/deactivates air quality /
pollution measurement.
Good air quality: 0–100
Medium air quality: 101–200
Poor air quality: 201–500
CAUTION: The activation of measurement increas
-
es battery consumption!
0 – OFF
1 – ON
* Premium version only.