Installation instructions
EN
Resistance table for Pt-1000 temperature sensors
Temp.
[°C]
Electrical
resistance
[Ω]
Temp.
[°C]
Electrical
resistance
[Ω]
Temp.
[°C]
Electrical
resistance
[Ω]
Temp.
[°C]
Electrical
resistance
[Ω]
-20
922
35
1136
90
1347
145
1555
-15
941
40
1155
95
1366
150
1573
-10
961
45
1175
100
1385
155
1592
-5
980
50
1194
105
1404
160
1611
0
1000
55
1213
110
1423
165
1629
5
1020
60
1232
115
1442
170
1648
10
1039
65
1252
120
1461
175
1666
15
1058
70
1271
125
1480
180
1685
20
1078
75
1290
130
1498
185
1703
25
1097
80
1309
135
1515
190
1722
30
1117
85
1328
140
1536
195
1740
Sensor T1 is not connected or is faulty.
- Heating: The controller switches on the circulation pump. In scheme 1, the mixing
valve opens and in schemes 2 and 3 it closes.
- Cooling: The controller switches off the circulation pump.
Sensor T2 is not connected or is faulty.
- Heating: The controller switches on the circulation pump. The mixing valve control
works.
- Cooling: The controller switches off the circulation pump.
OPERATION MODES WITH
SENSOR FAILURE
Содержание ACD20
Страница 1: ...ACD20 Constant temperature controller EN EN...
Страница 2: ......
Страница 4: ...4 EN...
Страница 41: ...41 Installation instructions EN CONTROLLER INSTALLATION Scheme Mixing valve position Ring position...
Страница 47: ...47 Instructions for use EN SCHEME 2 SUPPLY HEATING SCHEME 2 SUPPLY COOLING HYDRAULIC SCHEMES...
Страница 49: ...49 EN NOTES...
Страница 50: ...50 Instructions for use EN NOTES...
Страница 51: ......