7. Dixell temperature controller 

 

1592036010 XW70LH GB r1.0 14.02.2014.docx 

XW70LH 

1/5 

Digital controller for medium-low temperature 

refrigeration applications

 

XW70LH 

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be 

used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden 

temperature changes with high atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.p.A.” (see 

address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each 

other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with 

inductive loads could be useful. 

 

Dixell Srl reserves the right to change the composition of its products, even without notice, ensuring the 

same and unchanged functionality. 

2.

 

GENERAL DESCRIPTION 

Model 

XW70LH

, format 38x185mm, is microprocessor based controller, suitable for applications on 

medium or low temperature ventilated refrigerating units. It has  five  relay outputs to control 

compressor, fan, defrost, which can be either electrical or reverse cycle (hot gas) and light. The last 

one can be used as auxiliary output or for alarm signalling. It could be provided with a Real Time 

Clock which allows programming of up to 6 daily defrost cycles, divided into holidays and workdays. A 

“Day and Night” function with two different set points is fitted for energy saving. It is also provided with 

up to four NTC or PTC probe inputs, the first  one for temperature control, the second one, to be 

located onto the evaporator, to control the defrost termination temperature and to managed the fan. 

One of the 2 digital inputs can operate as third temperature probe. The fourth probe is used to signal 

the condenser temperature alarm or to display a temperature. 

The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  to a 

network line 

ModBUS-RTU

  compatible  such as the 

dIXEL 

monitoring units  of X-WEB family. It 

allows to program the controller by means the HOT KEY programming  keyboard.  

The instrument is fully configurable through special parameters that can be easily programmed 

through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed according to 

the temperature measured by the 

thermostat probe with a positive 

differential from the set point: if the 

temperature increases and reaches set 

point plus differential the compressor is 

started and then turned off when the 

temperature reaches the set point value 

again. 

Time

Temper.

Compr.

SET

ON

 

In case of fault in the thermostat probe the start and stop of the compressor are timed through 

parameters “

COn

” and “

COF

”. 

3.2

 

DEFROST  

Two defrost modes are available through the “

tdF

” parameter: defrost through electrical heater (

tdF = 

EL

) and hot gas  defrost (

tdF = in

). 

The defrost interval depends on the presence of the RTC (optional). If the RTC is present is controlled 

by means of parameter “

EdF

”:  

-

 

with EdF=in the defrost is made every “

IdF

” time – standard way for controller without RTC. 

-

 

with EdF = “rtc”, the defrost is made in real time depending on the hours set in the parameters 

Ld1..Ld6

 on workdays and in 

Sd1…Sd6

 in holidays;  

Other parameters are used to control defrost cycles:  its maximum length (MdF) and two defrost 

modes: timed or controlled by the evaporator’s probe (P2P).  

At the end of defrost dripping time is started, its length is set in the Fdt parameter. With Fdt =0 the 

dripping time is disabled. 

3.3

 

CONTROL OF EVAPORATOR FANS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC = C_n:

  fans will switch ON and OFF with the compressor and

 not run

 during defrost; 

FnC = o_n

  fans will run even if the compressor is off, and not run during defrost; 

After defrost, there is a timed fan delay allowing for drip time, set by means of the “

Fnd

” parameter. 

FnC = C_Y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC = o_Y

  fans will run continuously also during defrost 

 

An additional parameter “

FSt

” provides the setting of temperature, detected by the evaporator probe, 

above which the fans are always OFF. This is used to make sure circulation of air only if his 

temperature is lower than set in “FSt”. 

3.3.1  Forced activation of fans 

This function managed by the 

Fct

  parameter is designed to avoid short cycles of fans, that could 

happen when the controller is switched on or after a defrost, when the room air warms the evaporator. 

Functioning: 

if the difference of temperature between the evaporator and the room probes is more 

than the value of the Fct parameter, the fans are switched on. With Fct=0 the function is disabled. 

3.3.2  Cyclical activation of the fans with compressor off. 

When Fnc = c-n or c-Y (fans in parallel to the compressor), by means of the Fon and FoF parameters 

the fans can carry out on and off cycles even if the compressor is switched off. When the compressor 

is stopped the fans go on working for the Fon time. With Fon =0 the fans remain always off, when the 

compressor is off.  

3.4

 

AUXILIARY OUTPUT CONFIGURATION  

The functioning of the auxiliary relay (terminals. 20-21) can be set by the 

oA4 

 parameter,  according 

to the kind of application. In the following paragraph the possible setting: 

 

3.4.1  oA4 = AUS: Auxiliary thermostat  

I.E..

 anti condensing heater) with the possibility of switching it on and off also by keyboard 

 

Parameters involved:  

ACH 

Kind of regulation for the auxiliary relay: 

Ht: 

heating; 

cL: 

cooling

;

 

SAA 

Set point for auxiliary relay  

SHy 

Differential for auxiliary relay  

-

 ArP 

Probe for auxiliary relay  

Sdd 

Auxiliary output off during defrost

 

By means of these 5 parameters the functioning of the auxiliary relay can be set.. The differential is 

given by the 

SHy 

parameter. 

The auxiliary relay can be switched on also by the AUX button. In this case it remains on till it’s 

manually switched off. 

 

NOTE: 

Set 

Oa4 =AUS 

and 

ArP= nP 

(no probe for auxiliary output). 

In this case the relay 20-21 can be activated only by pushing the AUX button of the keyboard.  

 

3.4.2  oA4 = onF: On/off  relay  

In this case the relay is activated when the controller is turned on and de-activated when the controller 

is turned off. 

 

3.4.3  oA4 = db: Neutral zone regulation 

With 

oA4 = db

 the relay 20-21 can control a heater element to perform a neutral zone action. 

oA4 cut in = SET-HY 

oA4 cut out = SET  

 

3.4.4  oA4 = CP2: Second compressor  

With 

oA4 = CP2, 

the

 

relay 20-21 operates as second compressor:  it is activated in parallel with the 

relay of the first compressor, with a possible delay set in the 

AC1 

parameter. Both the compressors 

are switched off at the same time. 

 

3.4.5  oA4 = ALr: Alarm relay 

With 

oA4 = ALr 

the

 

relay 20-21 operates as alarm relay. It is activated every time an alarm happens. 

Its status depends on the 

tbA 

parameter: if “

tbA = y

”, the relay is silenced by pressing any key.  

If “

tbA 

n

”, the alarm relay remains on until the alarm condition recovers. 

 

3.4.6  oA4 = HES: Night blind management during energy saving cycles 

With 

oA4 = HES, 

the

 

relay 20-21 operates to manage the night blind: the relay is energised when the 

energy saving cycle is activated , by digital input, frontal button  or RTC (optional) 

4.

 

FRONT PANEL COMMANDS 

 

 

  Pour afficher et modifier le point de consigne. Dans le mode programmation, permet de 

sélectionner un paramètre ou de confirmer une opération. 

   

 

 

Pour démarrer un dégivrage. 

 

 

Pour afficher la température maximale enregistrée. Dans le mode programmation, permet 

de naviguer dans la liste des paramètres ou d'augmenter la valeur affichée.  

 

Pour afficher la température minimale enregistrée. Dans le mode programmation, permet 

de naviguer dans la liste des paramètres ou de diminuer la valeur affichée. 

 

 

Allume et éteint l'appareil, quand onF= oFF. 

 

 

 

Allume et éteint la lumière, quand oA3= Lig. 

AUX

  To switch the auxiliary relay, with oA3 or oA4 = AUS 

 

To switch the auxiliary relay, with oA3 or oA4 = AUS

 

 

KEY COMBINATIONS: 

  

 



To lock & unlock the keyboard

.

 

 

+

  

 

To enter in programming mode. 

  

+

  

 

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED  MODE 

FUNCTION 

 

ON 

Compressor enabled 

 

Flashing  Anti-short cycle delay enabled 

Changing parameters may affect the correct operation of the equipment. 

DO NOT modify the parameters if you are not completely sure. 

Содержание 2000152

Страница 1: ...3 2021 Pag 1 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www grupo selecta com ARMARIO REFRIGERA...

Страница 2: ...i n del personal 6 5 3 Utilizaci n con sustancias peligrosas 6 5 4 Mantenimiento 6 5 5 Garant a 6 Aviso a los clientes 6 6 Instalaci n 7 6 1 Emplazamiento 7 6 2 Conexi n a la red el ctrica 7 7 Regulad...

Страница 3: ...enido coincide con lo indicado en el apartado de la Lista de embalaje Si se observa alg n componente da ado o la ausencia de alguno avisar r pidamente al distribuidor No instalar ni utilizar el equipo...

Страница 4: ...rio dise ado para la conservaci n de productos farmac uticos medi camentos microtubos etc que requieran una temperatura constante a 4 C y donde se puedan dar fallos de alimentaci n que hagan peligrar...

Страница 5: ...com La tecnolog a nica en el mercado de almacenamiento de energ a frig or fica y la gran capacidad de aislamiento de su carcasa permite que la c mara mantenga la temperatura interior durante periodos...

Страница 6: ...o similar No utilizar disolventes agresivos 5 5 Garant a Este producto tiene una garant a de un a o La garant a no cubre los da os causados por uso indebido o causas ajenas a J P SELECTA s a u Cualqui...

Страница 7: ...ctrica Escoger una toma de corriente cercana al equipo y adecuada a la potencia del equipo Utilizar el cable de conexi n suministrado u otro de similares caracter sticas Para su seguridad la toma de...

Страница 8: ...los d as feriados La duraci n m xima est controlada por el par metro MdF mientras que el par metro P2P habilita la segunda sonda fin de deshielo a temperatura o queda deshabilitada fin de deshielo a...

Страница 9: ...FORMA MANUAL 1 Mantenga presionadas las teclas o y n durante algunos segundos hasta que aparezca el mensaje POF intermitente 2 Llegados a este punto el teclado ha quedado bloqueado solo se puede ver e...

Страница 10: ...del set point de las alarmas de temperatura y de la activaci n de los ventiladores ALd Retardo de la alarma de temperatura 0 255 min intervalo de tiempo entre la detecci n de una alarma de temperatur...

Страница 11: ...igital invierte el estado del rel auxiliar 8 7 INVERSI N DE LA ACCI N DEL CONTROLADOR FR O CALIENTE i1F o i2F Htr Hasta que la entrada digital se activa se invierte la acci n del controlador de fr o a...

Страница 12: ...ipci n Rango C F Nivel SET Set point LS US 5 0 rtC Men de visualizaci n Pr1 Hy Hist resis de regulaci n del compresor 0 1 25 5 C 1 255 F 2 0 Pr1 LS Set Point m nimo 50 C SET 58 F SET 50 0 Pr2 US Set P...

Страница 13: ...Minutos actuales 0 59 rtc dAY d as de la semana actual Sun SAt rtc Hd1 Primer d a festivo semanal Sun SAt nu nu rtc Hd2 Segundo d a festivo semanal Sun SAt nu nu rtc ILE Horario di inicio del ciclo de...

Страница 14: ...es contact with J P SELECTA s technical service Do not use the equipment in explosive flammable or corrosive atmospheres 2 Packing list Model 2000152 Shelves guides 2x 2000011 Shelves 2x 2000021 3 Tec...

Страница 15: ...12 14 16h 12h Ambient 25 C Ambient 20 C Temperatura interior Ejemplo de la evoluci n de la temperatura a dos condiciones ambiente distintas desde que se produce el fallo de alimentaci n OFF 4 Equipme...

Страница 16: ...ttp www grupo selecta com Unique on the market technology for storing cooling energy The high in sulation capacity of its casing allows the chamber to maintain internal tem peratures for periods of mo...

Страница 17: ...ator with a cloth and a cleaner or a similar solution Do not use aggressive solvents 5 5 Warranty This product is guaranteed for one year It does not cover damages caused by an incorrect use or causes...

Страница 18: ...at the rear part 6 2 Connection to the mains Plug the equipment to a near socket suitable for the equipment power Use the connection cable supplied or a similar one For your safety the equipment must...

Страница 19: ...ORATOR FANS The fan control mode is selected by means of the FnC parameter FnC C_n fans will switch ON and OFF with the compressor and not run during defrost FnC o_n fans will run even if the compress...

Страница 20: ...p pressed together for more than 3s the o and n keys till the Pon message will be displayed 6 9 THE CONTINUOUS CYCLE When defrost is not in progress it can be activated by holding the o key pressed fo...

Страница 21: ...bLL Compressor off with low temperature alarm of condenser n no compressor keeps on working Y yes compressor is switched off till the alarm is present in any case regulation restarts after AC time at...

Страница 22: ...imum current allowed for all the loads is 20A 12 1 PROBE CONNECTION The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid infiltration It is recommended to place th...

Страница 23: ...ary relay operating during defrost n y n Pr2 ALP Alarm probe selection nP P1 P2 P3 P4 P1 Pr2 ALc Temperat alarms configuration rE related to set Ab absolute Ab Pr2 ALU MAXIMUM temperature alarm Set 11...

Страница 24: ...MANUAL CODE 80412 REV 0 03 2021 Page 24 J P SELECTA s a u Autov a A 2 Km 585 1 Abrera 08630 Barcelona Espa a Tel 34 937 700 877 Fax 34 937 702 362 e mail selecta jpselecta es website http www grupo s...

Отзывы: