Schweitzer Engineering Laboratories, Inc.

SEL- 2664S Data Sheet

 5

Apply an SEL communications processor as the hub of a
star network, with point-to-point connection between the
hub and the SEL-2664S (see 

Figure 3

). 

The communications processor supports external
communications links including the public switched
telephone network for engineering access to dial-out
alerts and private line connections of the SCADA system.

Figure 3

Example Communications System

SEL manufactures a variety of standard cables for
connecting this and other relays to a variety of external
devices. Consult your SEL representative for more
information on cable availability.

SEL-2664S control logic improves integration in the
following ways.

Eliminates RTU-to-relay wiring with eight 
remote bits.

Set, clear, or pulse remote bits through

the use of serial port commands. Program the
remote bits into your control scheme with SEL

OGIC

control equations. Use remote bits for SCADA-type
control operations, such as trip and close.

Replaces traditional latching relays. 

Replace as

many as eight traditional latching relays for such
functions as “remote control enable” with latch bits.

Program latch set and latch reset conditions with
SEL

OGIC

 control equations. Use optoisolated inputs,

remote bits, or any programmable logic condition to set
or reset the nonvolatile latch bits. Each latch bit retains
its state when the relay loses power.

Eliminates external timers.

Replace external

timers for custom protection or control schemes
with eight general-purpose SEL

OGIC

 control equa-

tion timers. Each timer has independent time-delay
pickup and dropout settings. Program each timer
input with any element you need (e.g., time qualify
a current element). Assign the timer output to trip
logic, transfer trip communications, or other control
scheme logic.

Fast SER Protocol

SEL Fast SER Protocol provides SER events to an automated
data collection system. SEL Fast SER Protocol is
available on any serial port. Devices with embedded
processing capability can use these messages to enable
and accept unsolicited binary SER messages from the
SEL-2664S Relay. 

SEL relays and communications processors have two
separate data streams that share the same serial port. The
normal serial interface consists of ASCII character
commands and reports that are human readable through
use of a terminal or terminal emulation package. The
binary data streams can interrupt the ASCII data stream to
obtain information, and then allow the ASCII data stream
to continue. This mechanism allows use of a single
communications channel for ASCII communications
(e.g., transmission of a long event report) interleaved with
short bursts of binary data to support fast acquisition of
metering or SER data.

Ethernet Network Architectures

Figure 4

Simple Ethernet Network Configuration

Dial-Up ASCII Link

SCADA Link

SEL Communications Processor

ASCII Reports Plus
Interleaved Binary Data

SEL-2664S

IED

IED

IED

Cat 5 shielded twisted pair (STP) cables 

with RJ45 connectors (SEL-C627/C628) 

for copper Ethernet ports

OR

Fiber-optic Ethernet cables with

LC connectors (SEL-C808) for

fiber-optic Ethernet ports

NETWORK

Fiber only

Содержание SEL-2664S

Страница 1: ...ge elements Operator Controls Take advantage of multiple methods for accessing and using the operator interface of the relay The front and side panels have eight LEDs that indicate the ENABLED TRIP WA...

Страница 2: ...imple Network Time Protocol SNTP File Transfer Protocol FTP Telnet SEL ASCII SEL protocols including MIRRORED BITS communications Conformally Coated Overview Figure 1 Functional Diagram Operator Inter...

Страница 3: ...of the 64S elements described previ ously The combination of the two with their over lapping coverage provides 100 percent stator winding protection 100 percent of the time Neutral Ground Resistor Mo...

Страница 4: ...ry and Primary reference the Neutral Grounding Transformer NGT not CTN b Neutral current A sec is shown if CTN_LOC SEC otherwise it is hidden Table 1 Metered Quantities Sheet 2 of 2 Quantities Descrip...

Страница 5: ...ction or control schemes with eight general purpose SELOGIC control equa tion timers Each timer has independent time delay pickup and dropout settings Program each timer input with any element you nee...

Страница 6: ...ickSet in the following ways Develop settings offline with an intelligent settings editor that only allows valid settings Create SELOGIC control equations with a drag and drop text editor Configure pr...

Страница 7: ...under 26 V peak If a generator produces VN3 above this level even under normal load conditions the injection signal stops disabling the 64S elements However 59N1 59NRMS and 64F elements continue to pr...

Страница 8: ...for protection using redundant relays shown with neutral CTs on the secondary side of the neutral grounding transformer This application requires Relay 1 to set the Injection Source Mode setting MODE_...

Страница 9: ...for a typical example of the dc connections for 100 percent stator ground protection using the SEL 2664S Stator Ground Protection Relay stator to ground insulation resistance measurement and the SEL...

Страница 10: ...SEL 2664S Data Sheet Schweitzer Engineering Laboratories Inc 10 Relay Mounting and Dimensions Figure 15 SEL 2664S Wall Mount Dimensions Figure 16 SEL 2664S Connection Diagram for Wall Mount Option...

Страница 11: ...Engineering Laboratories Inc SEL 2664S Data Sheet 11 Figure 17 SEL 2664S Panel Mount Dimensions Figure 18 SEL 2664S Connection Diagram for Rack and Panel Mount Options Figure 19 SEL 2664S Rack Mount...

Страница 12: ...C Injection Source Connections Port 3 EIA 232 Serial Port Terminal C Neutral Current IN Connections Terminal B Power Supply 125 250 Vdc or 110 240 Vac Port 2 Fiber Optic EIA 232 Serial Port Terminal A...

Страница 13: ...40 Hz Maximum Open Terminal Voltage 26 V peak Protection Self protecting Power Supply Relay Start Up Time Approximately 5 10 seconds after power is applied until the ENABLED LED turns on High Voltage...

Страница 14: ...Telnet SNTP IEC 61850 MIRRORED BITS Operating Temperature IEC Performance Rating per IEC EN 60068 2 1 and 60068 2 2 40 to 85 C 40 to 185 F Not applicable to UL applications Operating Environment Insul...

Страница 15: ...mm2 14 AWG 2 1 mm2 Potential Voltage VN 16 AWG 1 3 mm2 10 AWG 5 26 mm2 Contact I O 18 AWG 0 8 mm2 14 AWG 2 1 mm2 a For all connection types the insulation voltage must be 300 V minimum Dielectric Str...

Страница 16: ...Ground 64S Pickup Range OFF 0 1 k 10 k primary Pickup Measurement Accuracy Steady State 10 of pickup 50 for pickup 2 k 15 pickup for 2 k pickup 10 k Time Delay Range 0 1 400 0 seconds Time Delay Accur...

Отзывы: