Sel SEL-2600 Скачать руководство пользователя страница 3

Date Code 20000525

SEL-2600 RTD Module

Installation

3

Installation

Step 1.

Locate an appropriate mounting panel or enclosure near the 
protected device.

Step 2.

Drill four mounting holes (see Figure 6 on page 14). 

Step 3.

Secure the SEL-2600 using the four bolts and locknuts provided.

Step 4.

Ground the SEL-2600 by connecting Terminal 26 to an 
appropriate electrical ground.

Step 5.

Connect as many as 12 RTDs to the SEL-2600 terminal blocks 
(see Figure 5 on page 13).

Step 6.

Record the type and location of each RTD in Table 1 on page 4.

Step 7.

Connect a dry contact to the SEL-2600 contact input Terminals 20 
and 21 as appropriate.

!

CAUTION:

 Do not connect ac or dc voltage to the contact input.

Step 8.

SEL-701 Motor Relay Application

Connect the SEL-2600 to the SEL-701 Motor Relay using a 
single fiber-optic cable (SEL part number C801FZ or 
C801FD). Follow the SEL-701 setting instructions in 
SEL-701 Motor Relay Application on page 4.

SEL-2030 Communications Processor Application

Connect the SEL-2600 to the SEL-2030 Communications 
Processor using a single fiber-optic cable and a fiber-optic 
transceiver as outlined in SEL-2030 Communications Proces-
sor Applications on page 6
.

Step 9.

Connect ac line power to the SEL-2600 through Terminals 23 and 
24 (120 Vac) or Terminals 23 and 25 (250 Vac). The green 
ENABLE LED illuminates when ac power is applied and the 
internal diagnostics are complete.

Step 10.

Verify the SEL-2600 is operating properly.

The green ENABLE LED is illuminated.

The red TX LED pulses twice per second.

The red INPUT LED illuminates when the SEL-2600 contact 
input is energized.

The SEL-701 or SEL-2030 receives valid RTD measure-
ments.

Содержание SEL-2600

Страница 1: ...built into each device and also connects to the SEL 2030 Commu nications Processor using a single SEL 2800 Fiber Optic Transceiver The fiber optic link eliminates expensive cable pulls and provides e...

Страница 2: ...relay as directed in SEL 701 Motor Relay Application on page 4 NOTE The SEL 701 front panel may display RTD Failure if the correct RTDs are not yet connected The SEL 701 METER T report displays the R...

Страница 3: ...ion Connect the SEL 2600 to the SEL 701 Motor Relay using a single fiber optic cable SEL part number C801FZ or C801FD Follow the SEL 701 setting instructions in SEL 701 Motor Relay Application on page...

Страница 4: ...tor Relay accurately tracks the heating effects of overloads and unbalance current Combining the SEL 2600 and the SEL 701 Motor Relay enhances this list of protection features by adding remote RTD bas...

Страница 5: ...his enables use of the external module data Set the RTD Location and RTD Type settings based on the information you recorded in Table 1 on page 4 Finally set the RTD Alarm and Trip Temperature setting...

Страница 6: ...s Step 1 Receive temperature data from the SEL 2600 Step 2 Store the temperature data in memory Step 3 Perform temperature threshold comparisons Step 4 Issue control commands to a protective relay bas...

Страница 7: ...587 or SEL 387 Relay SCADA EIA 232 PC HMI SEL 2800 Fiber Optic Transceiver SEL 2030 Communications Processor SEL 501 Relay SEL 2600 RTD Module Motor Load EIA 232 SCADA PC HMI SEL 2800 Fiber Optic Tran...

Страница 8: ...r in the form n USER offset where n is the port number and offset is the value shown in the offset column of Table 2 on page 9 For example access the RTD 2 10 ohm copper data using the absolute addres...

Страница 9: ...Ds Use the SET A command to reserve additional registers for mathematical equations SET A USER 4 USER 57 Table 2 SEL 2030 Communications Processor Memory Map Address hex Offset Data Description F800h...

Страница 10: ...ogic bit transitions Use the SET L command to control four breakers using fast operate commands based on the result of a single temperature comparison The following example settings assume the relay i...

Страница 11: ...ng of Message Code 74h 1 byte Message Length 116 bytes 0000000000h 5 bytes Routing Value 0 00h 1 byte Status Byte 12h 1 byte Function Code 00h 1 byte Sequence Byte 00h 1 byte Pad Byte xxxxxxx 4 bytes...

Страница 12: ...data communications using CRC 16 Cycli cal Redundancy Check error detection Module shall be equipped with a fiber optic port Module shall use LEDs Light Emitting Diodes to indicate device self test st...

Страница 13: ...1 12 13 14 15 16 17 18 19 20 21 22 RTN RTN RTN RTN RTN RTN N C IN IN N C 120 Vac N N C 23 24 25 26 N C N 240 Vac RTD1 RTD2 RTD3 RTD4 RTD5 RTD6 CONTACT INPUT AC POWER 27 28 29 30 31 32 33 34 35 36 37 3...

Страница 14: ...20000525 Mechanical Diagram 14 Mechanical Diagram Figure 6 SEL 2600 Mechanical Diagram 0 203 5 16 mm 4 418 112 22 mm Top View End View 9 000 228 60 mm 1 750 44 45 mm 8 515 216 28 mm 9 500 241 30 mm 2...

Страница 15: ...V m 900 MHz with modulation Cold IEC 60068 2 1 1990 Test Ad 16 hr 40 C Dry Heat IEC 68 2 2 1974 Test Bd 16 hr 85 C Damp Heat Cyclic IEC 60068 2 30 1980 Test Db 55 C 6 cycles 95 humidity Dielectric Str...

Страница 16: ...ring in this document are the trademark or registered trademark of their respective holders U S and Foreign Patents Pending The software firmware schematic drawings module commands and module messages...

Отзывы: