0000137630 Rev. 2.0 16
12.
Parameter List
Parameter
Value
Value
Value
Value
Value
Value
Default
1
Language
english
german
italian
english
2
Password
0 - 9999
0 (disabled)
3
Statistics
dosing hours tubing hours liters
4
Max flow rate
0.1 –
100.0%
100.0%
5
Pump Function
Manual
Mode
mA Mode
Batch Mode 1 :N Mode
N :1 Mode
Ppm Mode
Manual Mode
6
Alarm Relay
N. Open
N.Closed
N.Open
7
Level Alarm
Stop
Run
Stop
8
Buzzer
ON
OFF
OFF
9
Unit
ml/h
L/h
%
ml/h
10
Trigger
No Trg
Trg 1
Trg 2
Trg 1&2
No Trg
11
Density
0.50-2.00
1.00
12
On Time
0-10000
10
13
Off Time
0-10000
0
14
Delay Time
0-10000
0
15
mA for 0%
0.0-20.0
4.0
16
mA for max
0.0-20.0
20.0
17
N
1-1000
1
18
pulse
1-2000
1
19
liter
1-2000
1
20
Chem. Conc.
1-100
100
21
ppm
0-3000
1000
22
memory
ON
OFF
OFF
23
quantity
0-30000
1
24
time
0-10000
1
25
Flow rate
Calibr.
10000
13.
Dosing parameter Table
Mode
Param 1
Param 2
Param 3
Memory
Trigger
Max flow
rate
Density
Manual
ON Time sec
(
0
-10000)
OFF Time
sec
(
0
-10000)
DELAY Time
sec (
0
-10000)
TRIGGER
(
No Trg
/Trg
1/Trg 2/Trg
1&2)
MAX FLOW
RATE
(0.1 –
100
%
)
Direct or Inverse
mA
mA Input for
min dosing
(
0.0
-20.0 mA)
mA Input for
max dosing
(0.0-
20.0
mA)
TRIGGER
(
No Trg
/Trg
1/Trg 2/Trg
1&2)
MAX FLOW
RATE
(0.1 –
100
%)
PPM
Set Point
(
1
-3000 ppm)
Flowmeter
factor
(
1
-2000 pul /
1
-2000 Lit)
CHEM.
CONC.
(1-
100
%)
MEMORY
(ON-
OFF
)
TRIGGER
(
No Trg
/Trg
1/Trg 2/Trg
1&2)
DENSITY
(0.50 – 2.00
kg/L)
1.00
Batch
Quantity
(
1
-30000ml)
Time sec
(
1
-10000)
MEMORY
(ON-
OFF
)
DENSITY
(0.50 – 2.00
kg/L)
1.00
PROP 1:N
N
(
1
-1000)
MEMORY
(ON-
OFF
)
TRIGGER
(
No Trg
/Trg
1/Trg 2/Trg
1&2)
PROP N:1
N
(
1
-1000)
MEMORY
(ON-
OFF
)
TRIGGER
(
No Trg
/Trg
1/Trg 2/Trg
1&2)
Default parameters are typed bold and underlined
14.
Alarms Table
alarm
dosing
Display
buzzer
Relay
Tube Break
stop
TUBE BREAK
ON if selected
ON if selected
Level
Stop if selected
LEVEL
ON if selected
ON if selected
Motor
stop
MOTOR
ON if selected
ON if selected
Содержание KRONOS 50
Страница 2: ...0000137630 Rev 2 0 ...