0000137630 Rev. 2.0 13
Paragraph 7
Programming
Operation
This makes it possible to set the density of the chemical
product.
Paragraph 8
Programming
Operation
This makes it possible to set the input triggers.
When the triggers are present, gives consent to the pump
to run, depending the setting pump function:
•
No Trg=
the triggers are disabled.
•
Trg 1=
the pump run when only the trigger 1 is
enabled.
•
Trg 2=
the pump run when only the trigger 2 is
enabled.
•
Trg 1&2=
the pump run when the both triggers
(1&2) are enabled.
Paragraph 9
Programming
Operation
This makes it possible to set unit of measurement, which
can be:
•
L/h= liter per hour.
•
ml/m= milliliter per minute.
•
Gph= Gallon per hour.
•
%= the percentage of the maximum flow-rate.
Paragraph 10
Programming
Operation
The buzzer is active when there is an alarm condition.
This makes it possible to set the buzzer the system to On
or Off.
Paragraph 11
Programming
Operation
This makes it possible to set the level alarm as follow:
•
Stop=
the pump stops.
•
Run=
the pump keeps running.
Density
1.00 kg/L
Triggers
No Trg
Units
L/h
Buzzer
Off
Level Alarm
Stop