TAG02M0000SE 035670 161120
9
memorize the schedule set and the word ‘
MEMO
’ will
appear on the display; the device will automatically exit the
schedule programming mode.
WARNING
- If you want to reset the time intervals to factory settings,
please reach the user parameter ’dFLt’ (the default
data); In this case, all user parameters will be reset to
factory settings.
- If you exit the time programming without pressing the
’OK’ button, or you do not save the settings, the time
program will NOT be saved in memory and the previous
program will be restored.
Changes are stored in memory only when the if you
enable this operation with the phase characterized by
the word ’MEMO’.
‘AFr’ ANTIFREEZE SETTING
The Antifreeze function allows you to select a minimum
temperature to be maintained when the programmable
thermostat is off, so as to protect both the room and the
equipment when the room temperature falls below the set
value.
The device leaves the factory with the Antifreeze function set
on 3°C.
IMPORTANT: the function is active only when the device
has been set in the heating mode.
To set the Antifreeze temperature, carry out the following steps:
1.
Select the parameter ‘
AFr
’ and press the ‘
OK
’ button.
2.
The display shows the Antifrost temperature previously set
and the ‘
P
‘ icon flashes.
3.
Press buttons ‘ ‘ and ‘
‘ to change the setting (between
OFF, 0.5°C..25°C);
every change will be automatically
memorized
.
4.
To return to the list of user parameters, press the ‘
OK
’
button.
5.
To exit the user parameters setting and resume normal
operation, press the ‘ ‘ button or wait 10 seconds without
pressing any key.
‘ d1 ‘ SETTING FIRST STAGE DIFFERENTIAL
The setting of this parameter allows to define the value in °C
which elapses between the power on and power off of the
programmable thermostat first stage regarding the set room
temperature (for further details see paragraph ‘ Operation of
the first and second stage ‘).
To adjust the differential related to the first stage follow these
instructions:
1.
Select the parameter ‘
d1
’ and press the ‘
OK
’ button.
2.
The display shows the previously set temperature and the
blinking icon ‘
P
‘.
3.
Push the buttons ‘
‘ and ‘
‘ to modify the value (included
in 0,1°C..d12);
every update is stored automatically
.
4.
In order to go back to the user parameters list, push the
‘
OK
’ button.
5.
To exit from the setting of the user parameters and reset the
normal operation, push the button ‘
‘ or wait 10 seconds
without pushing any button.
‘ d2 ‘ SETTING SECOND STAGE DIFFERENTIAL
Setting this parameter allows to define the value in °C which
elapses between the power on and the power off of the
programmable thermostat second stage regarding the set
room temperature, considering the parameters ‘ d1 ‘ and ‘ d12 ‘
(for further details see paragraph ‘ Operation of the first and
second stage ‘).
To adjust the differential related to the second stage follow
these instructions:
1.
Select the parameter ‘
d2
’ and press the ‘
OK
’ button.
2.
The display shows the previously set temperature and the
blinking icon ‘
P
‘.
3.
Push the buttons ‘
‘ and ‘
‘ to modify the value (included
in 0,1°C..15°C);
every update is stored automatically
.
4.
In order to go back to the user parameters list, push the
‘
OK
’ button.
5.
To exit from the setting of the user parameters and reset the
normal operation, push the button ‘
‘ or wait 10 seconds
without pushing any button.
‘ d12 ‘ SETTING THE DIFFERENTIAL BETWEEN FIRST
AND SECOND STAGE
The setting of this parameter allows to define the value in °C
which elapses between the power off of the first stage and the
power off of the second stage of the programmable thermostat
(for further details see paragraph ‘ Operation of the first and
second stage ‘).
To adjust the differential between the first and the second
stage, follow these instructions:
1.
Select the parameter ‘
d12
’ and press the ‘
OK
’ button.
2.
The display shows the previously set temperature and the
blinking icon ‘
P
‘.
3.
Push the buttons ‘
‘ and ‘
‘ to modify the value (included
in d1..15°C);
every update is stored automatically
.
4.
In order to go back to the user parameters list, push the
‘
OK
’ button.
5.
To exit from the setting of the user parameters and reset the
normal operation, push the button ‘
‘ or wait 10 seconds
without pushing any button.
‘ tMr2 ‘ FIRST AND SECOND STAGE TIMER SETTING
This parameter allows to define the activation time (in seconds)
of the second stage if the first stage is previously activated.
In order to adjust the timer perform the following operations:
1.
Select the parameter ‘
tMr2
’ and press the ‘
OK
’ button.
2.
The display shows the previously set time expressed in
seconds and the blinking icon ‘
P
‘.
3.
Push the buttons ‘
‘ and ‘
‘ to modify the value (included
in 0 .. 200 seconds);
every update is stored automatically
.
4.
In order to go back to the user parameters list, push the
‘
OK
’ button.
5.
To exit from the setting of the user parameters and reset the
normal operation, push the button ‘
‘ or wait 10 seconds
without pushing any button.
‘ OFS1 ’ REMOTE SENSOR OFFSET SETTING
With this parameter it is possible to correct the temperature
reading of the remote sensor by ±5°C in order to correct any
systematic reading errors due to the positioning of the remote
sensor in areas unsuitable for measuring the room temperature.
The device leaves the factory with the Offset set at 0.0°C.
To adjust the Offset value for the remote sensor, carry out the
following steps:
1.
Select the ‘
OFS1
’ parameter and press the ‘
OK
’ button.
2.
The display shows the Offset temperature previously set
and the ‘
P
‘ icon flashes.
3.
Press buttons ‘ ‘ and ‘
‘ to modify the setting (range:
-5.0°C .. +5.0°C);
every change will be automatically
stored in memory.
4.
To return to the list of user parameters, press the ‘
OK
’
button.
5.
To exit the user parameter settings and resume normal
operation, press the ‘ ‘ button or wait 10 seconds without
pressing any key.
‘H-C’: HEATING / COOLING SETTING
This setting is used to invert the operating logic of the relay
according to whether a heating or air conditioning unit is being
controlled.
IMPORTANT: The programmable thermostat leaves the
factory set in the heating mode.
To modify the operating logic, carry out the following procedure:
1.
Select the parameter ’
H-C
’ and press ’
OK
’; the display shows
the current adjustment mode and the ‘
P
‘ icon flashes.
2.
Press the buttons ‘
’ and ‘
’ to select the desired