TAG02M0000SE 035670 161120
10
adjustment;
each change is automatically saved.
3.
To return to the list of user parameters, press the ‘
OK
’
button.
4.
To exit the user parameter settings and resume normal
operation, press the ‘ ‘ button or wait 10 seconds without
pressing any key.
During normal operation, if the heating mode is on, the ‘
‘ icon
will remain lit, whereas if the cooling mode is on, the ‘
‘ will
remain steadily lit.
‘ StM ‘ SUMMER TIME SETTING
Setting this parameter allows the automatic update when
switching from Winter Time to Summer Time and the other way
around.
In order to adjust this parameter follow these instructions:
1.
Select the parameter ‘
StM
’ and press the ‘
OK
’ button.
2.
The display shows the previously set option and the blinking
icon ‘
P
‘.
3.
Push the buttons ‘
‘ and ‘
‘ to modify the value (included
in
EnA
: parameter enabled ..
dIS
: parameter disabled);
every update is stored automatically
.
4.
In order to go back to the user parameters list, push the
‘
OK
’ button.
5.
To exit from the setting of the user parameters and reset the
normal operation, push the button ‘
‘ or wait 10 seconds
without pushing any button.
‘ dFLt ’ SET DEFAULT DATA
With this parameter it is possible to reset user parameters in
order to bring back all the parameters to factory default.
Here below are the default parameters data:
PARAMETER
DEFAULT
PrOG
Monday-Friday
TIME INTERVALS PRESET
Comfort mode
Economy mode
6.00 .. 8.00
8.00 .. 11.00
11.00 .. 13.00
13.00 .. 17.00
17.00 .. 23.00
23.00 .. 6.00
Saturday-Sunday
TIME INTERVALS PRESET
Comfort mode
Economy mode
6.00 .. 8.00
8.00 .. 11.00
11.00 .. 13.00
13.00 .. 17.00
17.00 .. 23.00
23.00 .. 6.00
AFr
3.0°C
d1
0.2°C
d2
0.2°C
d12
3.0°C
tMr2
0 seconds
OFS1
±5°C
H-C
HEAt (heating)
StM
EnA (enabled)
WARNING
The Default Data setting does not modify the values
previously set of Time and date, Set-Point and settable
minimum and maximum limits of the SET-POINTs
themselves.
Proceed as follows:
1.
Select the parameter ’
dFLt
’ and press ’
OK
’; the device
automatically sets the default data and the display will show
’-dF-’ and the ‘
P
‘ icon flashes.
2.
To quit the user parameter settings press the ‘
OK
’ button or
wait 10 seconds without pressing any key.
3.
To reset the normal operation press the ‘
OFF
’ button.
4.
The programmable thermostat is off; in order to activate it
press the button ‘
’.
WARNING!
Restoring the Default Data will reset all settings made
by the user, such as Time Program, Heating/Cooling,
Set-Points and all other programmable data.
OPERATION OF THE FIRST AND SECOND STAGE
1° Stage
: Output ‘STAGE I‘
2° Stage
: Output ‘STAGE II‘
Sp
:
Set-Point temperature
Ts
:
Temperature detected by the remote sensor
OFS1
: Offset remote sensor (± 5,0°C)
d1
:
Differential of the 1° asymmetrical stage (0,1 .. 15,0°C)
d2
:
Differential of the 2° asymmetrical stage (0,1 .. 15,0°C)
d12
:
Differential between 1° and 2° stage (0,1 .. 15,0°C)
Heating mode
When on heating mode and the first stage relay is active on the
display appears the icon ‘ ‘ in continuous mode; if also the
second stage is activated the same icon blinks.
Cooling mode
When on cooling mode and the first stage relay is active, on the
display appears the icon ‘ ‘ in continuous mode; if the second
stage is also activated, the same icon blinks.
FAN OUTPUT
The output ‘ ’, terminals 12 and 13, is activated / deactivated
at the same time with activation / deactivation of the output
‘STAGE I‘ (first stage), only in cooling mode.
BLOCK CIRCUIT AND RESET
The reset circuit is completely separated from the programmable
thermostat and works with 230V voltage.
It is used primarily on gas heating systems where the burners
send the “block” signal and use a button to re-initialize the
starting sequence.