8. Controller
The display is used to
Control / Alarm Set Point Settings
Temperature Readings
Alarm Readings
The main menu will display the following by default
TEMP READINGS: temperature readings and alarm display
TEMP SETPOINTS: to change set points by pressing UP or DOWN button and SET to choose an option
TEMP READINGS showing the temperature readings and any alarms. Each alarm will be shown by flashing
every few seconds.
The example is showing a communication loss with the inverter alarm.
Press MENU to return to the main menu.
List of possible alarms which generate an alarm condition
ALARM COMPRESSOR
ALARM INT BLOWER
ALARM AMB BLOWER
ALARM HIGH TEMP
High Temperature Alarm
ALARM INV COMMS
No Communication with Inverter Alarm
ALARM SENS FAIL
Temperature Sensor Fail Alarm
ALARM LOW TEMP
Low Temperature Alarm
ALARM CONT COMMS
No Communication with Main Controller Alarm
List of possible warnings which do not generate an alarm condition
WARNG COMPRESSOR
WARNG INT BLOWER
WARNG AMB BLOWER
DOOR CONTACT
Door Contact Open