Seifert 862504S62 Скачать руководство пользователя страница 1

Version No. 1-6 - 13.08.2021

Doc. No. 99862504S62

1 / 21

Table of Content 862504S62

1. User manual 

2

 .................................................................................................................................. 

2. Legal Regulations 

2

 ........................................................................................................................ 

3. Safety Instructions 

3

 ...................................................................................................................... 

4. Functional Principle 

4

 ..................................................................................................................... 

5. Technical Data 

5

 .............................................................................................................................. 

6. Mounting Principle 

6

 ....................................................................................................................... 

7. Electrical Connection 

10

 ................................................................................................................. 

8. Controller 

12

 .................................................................................................................................... 

9. Wiring Diagram 

16

 .......................................................................................................................... 

10. Taking into Operation 

17

 ............................................................................................................. 

11. Trouble Shooting 

18

 ..................................................................................................................... 

12. Maintenance & Cleaning 

19

 ......................................................................................................... 

13. Transport & Storage 

20

 ................................................................................................................ 

14. Parts supplied / Spare parts / Accessories 

21

 .......................................................................... 

 

Содержание 862504S62

Страница 1: ...ions 2 3 Safety Instructions 3 4 Functional Principle 4 5 Technical Data 5 6 Mounting Principle 6 7 Electrical Connection 10 8 Controller 12 9 Wiring Diagram 16 10 Taking into Operation 17 11 Trouble...

Страница 2: ...ons in the instruction manual must be adhered to General danger Indicates compulsory safety regulations which are not covered by a speci c pictogram such as one of the following High electric voltage...

Страница 3: ...d with regards to Safety instructions Instructions on taking the cabinet out of operation Instructions on the prevention of unauthorised cabinet reconnection The electric equipment meets the valid saf...

Страница 4: ...t thus taking it to high pressure and high temperature and pushes it through the condenser where it is cooled by ambient air thus passing from the gas to the liquid state At the liquid state it then p...

Страница 5: ...1200 m h Cabinet air circuit 500 850 m h Mounting Wall mounted Recessed Housing Material Stainless steel AISI 304 V2A Dimension A x B x C D E 1 350 x 395 x 210 55 155 mm Weight 45 kg Cut Out Dimension...

Страница 6: ...after installation Use only the supplied mounting hardware Tighten Screws to 4 5 Nm Ensure the mounting surface does not warp after assembly and reinforce it if necessary 1 M6 screws 2 M6 toothed wash...

Страница 7: ...internal and external are not obstructed It must also be ensured in accordance with UL that the air outlet is not blowing air directly at an equipment operator Should this be the case a barrier or duc...

Страница 8: ...No 1 6 13 08 2021 Doc No 99862504S62 8 21 Cold air outlet duct When using an co d air outlet duct please follow the steps below Filter installation If you install replace a lter please follow the step...

Страница 9: ...d condensate evaporation of the cooling unit releases the condensate to the environment If condensate formation is too great additional condensate can drip into an over ow trough which then drains o o...

Страница 10: ...250Vac 30000 cycles These contacts are not suitable for uorescent loads neon lights etc that use starters ballasts with phase shifting capacitors Fluorescent lamps with electronic controllers or with...

Страница 11: ...Version No 1 6 13 08 2021 Doc No 99862504S62 11 21...

Страница 12: ...shown by ashing every few seconds The example is showing a communication loss with the inverter alarm Press MENU to return to the main menu List of possible alarms which generate an alarm condition A...

Страница 13: ...T ALR L Low Alarm Set Point SETPOINT HEAT Heater Set Point SETPOINT SEL Select between Modbus Display set points or Onboard Potentiometer TEMP SEL Select between Celsius or Fahrenheit Press MENU to re...

Страница 14: ...erature press the SET button and an S will be shown in the display Press MENU to return to the TEMP SETPOINTS screen SETPOINT TYPE showing which set point type is chosen Set point type can be modi ed...

Страница 15: ...needs to be pressed for at least 2 seconds and the total sequence need to be done in 20 seconds When entering the sequence the display shows that the sequence is being registered if after pressing th...

Страница 16: ...Version No 1 6 13 08 2021 Doc No 99862504S62 16 21 9 Wiring Diagram Power connector 1 L1 2 3 N 4 PE Signal connector 1 Alarm NC 2 Alarm COM 3 Alarm NO 4 Door contact 5 Door contact...

Страница 17: ...be protected with a MCB Type D or K Upon connection the internal fan will start working If the temperature inside the enclosure is higher than the set value of the controller both the compressor and e...

Страница 18: ...Install the unit at a di erent place The ambient temperature must be within the stated operating temperature range The control cabinet is not sealed properly The control cabinet needs re sealing Fan o...

Страница 19: ...be replaced immediately Do not use a steam jet or high pressure to clean the lter mats Do not wring out the lter mats If the ambient air is extremely oily we recommend the use of metal lters see acce...

Страница 20: ...g conditions temperature range 40 C to 70 C relative humidity at 25 C max 95 the cooling unit should always be stored according to the installation position Returning the unit To avoid transport damag...

Страница 21: ...Hal Far Industrial Estate North Kingstown Wantirna South 42477 Radevormwald Birzebbuga BBG 3000 4563 Gerla ngen 4901 Ottnang 26100 Cremona RI 02852 3152 Victoria Germany Malta Switzerland Austria Ital...