TB XRI1-IR 02.00 E
13
5.2
Dip switches
Behind the front plate of the
XRI-IR
relay there is one
dip switch to preset the following functions:
•
Password programming
•
Output relay functions
The following table 5.1 shows the position and desig-
nation of the code jumpers:
5.2.1
Function of the output relays
The alarm relays are activated according to the preset-
ting:
Dip switch
3
OFF:
All output relays will be reset automatically after the
fault has been cleared, (e.g. when the fault current is
interrupted).
Dip switch 3 ON:
All output relays remains activated and must be reset
after fault clearence.
•
Manually: By pressing push button
<SELECT/RESET>
•
External: By connecting aux. voltage to C2/C2L
or C2/C2H
•
Via RS 485 interface
To let the parameter change take effect, the auxiliary
voltage has to be switched on and off again after the
dip switches are plugged or unplugged.
Dip
switches
Function
Code
jumper position
Operation mode
1
Password
OFF
Normal position
ON
Password selection
2
none
3
Reset
OFF
Output relays will be reset automatically
ON
Output relays will be reset manual/external/via software
4
none
Tab. 5.1: Summary of coding possibilities