32
TB XRI1-IR 02.00 E
8.8
System data and test specifications
Design standards:
Generic standard:
EN 50082-2, EN 50081-1
Product standard:
EN 60255-6, IEC 255-4, BS142
Specified ambient service
recommended temperature for operation:-10°C to +55°C
temperature limits:
in operation -25°C to +70°C
in storage -25°C to +70°C
Moisture-carrying capacity class F
as per DIN 40040 and per DIN
IEC 68, part 2-3:
rel. humidity <95% at 40°C for 56 days
Insulation test voltage, inputs and
outputs between themselves and
to the relay frame as per EN 60255-6,
IEC 255-5:
2.5 kV (eff.) / 50 Hz.; 1 min.
Impulse test voltage, inputs and
outputs between themselves and
to the relay frame as per
EN 60255-6, IEC 255-5:
5 kV; 1.2/50 µs, 0.5 J
High frequency interference test
voltage, inputs and outputs between
themselves and to the relay frame as
per EN 60255-6, IEC 255-6:
2.5 kV/1 MHz
Electrical discharge (ESD)
test as per EN 61000-4-2,
IEC 255-22-1:
8 kV air discharge, 6 kV contact discharge
Electrical fast transient (Burst)
test as per EN 61000-4-8,
IEC 255-22-1:
4 kV/2.5 kHz, 15 ms
Power frequency magnetic
100 A/m continuously
field immunity test:
1000 A/m for 3 s
Radiated electromagnetic field disturbance
test as per ENV 50140, IEC 255-22-3: electric field strength: 10 V/m
Guided radiated electromagnetic field
disturbance test as per ENV 50141:
electric field strengh: 10 V/m
Surge immunity test as per
EN 61000-4-5:EN 61000-4-5:
4 kV
Radio interference suppression
test as per EN 55011:
limit value class B
Radio interference radiation
test as per EN 55011:
limit value class B
Содержание XRI1-IR