8.4 Auto Calibration Mode (AUTO CAL)
In case of using AUTO CAL function , control position and function necessary in adjustment
can be set automatically. 5-10 minutes are required and according to driving size, the requiring time
can increased or decreased.
* After executing initially , " ALL" should be executed .
8.4.1 Auto PV Calibaration ( AUTO PV )
AUTO PV re-set Zero Point (0%) and End Point (100%) only.
→
Execute AUTO CAL without changing existing parmeter value.
It is used when the positioner's installation position is slightly changed.
<ENTER>
<ENTER>
X
AUTO ALL
○
○
○
○
○
○
AUTO PV
○
○
X
X
X
Zero Point End Point
P,I,D
RA / DA
BIAS
V_O
29/40
<ENTER>
5 seconds
Automatically setting
for dozens of seconds
→
8.4.2 AUTO ALL
Set all parameter values suitable to Zero Point, End Point,
and parameter value suitable to driving facility.
<ENTER>
<ENTER>
Automatically setting
for dozens of minutes
→
→
→
<ENTER>
<ENTER>
→
→
→
29/40