20
TB MRD1-T 10.01 E
5.1.2
Parameter sets
MRD1
has access to four independent parameter
sets. Each of these data sets comprises a complete
parameter set which makes individual setting of the
MRD1
possible. If required by the operational pro-
cedure several different settings can be stored and
then called off when needed.
Data of SYSTEM parameters (e.g. rated frequency,
slave address, date, time etc.) are not filled in the
four parameter sets, they do always apply.
EDIT-
memory
display / keyboard
serial interface
parameter set
1
parameter set
2
parameter set
3
parameter set
4
protection-
program
output
relay
message
display / LED
measurement
switch open in
Offline Test Mode
SYSTEM-
parameter
transformer
Fig. 5.1.2: Parameter sets, principle
For processing the selected set is loaded into the
EDIT memory (switch: Set to Edit). After parameters
have been changed, the EDIT memory is completely
restored in the parameter set memory. All changes
are then jointly read-in.
Another switch (Work Set) defines on which of the
data sets the protection program is based. All
switches are adjusted via software.
OFFLINE TEST mode is specified in chapter 5.1.6.