54
TB MRD1-T 10.01 E
7
Commissioning
7.1
Check list
Check
Remark
ok.
Safety Measures
Observe relevant safety regulations
Aux. voltage range
Prior to connection it has to be checked whether existing aux. voltage is
within the permissible range for MRD1
Rated system data
Secondary currents of CTs provided in the system have to be in compli-
ance with rated currents of the MRD1 (1 A or 5A) in the respective wind-
ing
Connection
Check MRD1 for correct connection in the switchboard
Entry of rated system
data
Has all rated system data correctly been programmed ?
Are the indices of the vector group setted.
Are the CTs connected normal or revers
Setting of parame-
ters for protection
Have all parameters for protection correctly been programmed ?
Reset time
Are the reset times set to all output relays?
Selection of work
parameter set
Has the right parameter set been selected as working set?
Protection function
Does LED SELF-TEST light up green and is Selftest relay energized ?
Device tests
Selftest routines
- Lamptest
- Test of the output relays
- Checksum test
- Test of the working parameter set in OFFLINE TEST mode