34
TB MRD1-T 10.01 E
Key
D
isplay
Parameter
A
vailable
in
MRD1
-
T2 T3
Select
Setting range
(
•
no selection)
Default
a
ctual
Set 1
S
et 2
S
et 3
S
et 4
connection system of winding 1
××
wye, delta, zigzag,
wye+n, n
wye + n
corresponding to winding 2
××
wye, delta, zigzag,
wye+n, n
wye + n
phase shift in winding 2 in
×
30
°
in relation to winding 1
××
0-11
0
connection system in winding 3
×
wye, delta, zigzag,
wye+n, n
wye + n
phase shift in winding 3 in
×
30
°
in relation to winding 1
×
0-11
0
voltage displacement by transformer
tap changer in winding 1
××
- 20 %...+ 20 %
0
,0
Winding 1 CT connection in nor-
mal polarity (like connection dia-
gram) or inverted (reverse polarity)
"
××
normal,
inverted
normal
corresponding to winding 2
"
××
normal,
inverted
normal
corresponding to winding 3
"
×
normal,
inverted
normal
"
NOTE: The Parameter must be set to inverted polarity, if the direction of current flow in the secondary circuit is reverse to
the input terminals of
MRD1
according to the
connection diagram (Chapter 10).