TB MRU3-2 12.00 E
31
7.3.2
Parameter for the fault recorder
Function
Parameter
Adjustment example
FR
Number of recordings
(1)*2 x 8 s; (3)*4 x 4 s; (7)*8 x 2 s (50 Hz)
(1)*2 x 6.66 s, (3)*4 x 6.66 s, (7)*8 x 1.66 s
(60 Hz)
FR
Savings of the recording at the occurence
P_UP; TRIP; A_PI; TEST
FR
Pre-trigger-time
0.05 s – 8.00 s
* is written over when a new trigger signal arrives
7.4
Output relays
Trip relays/change-over contacts
Alarm relaya/change-over contacts