16

TB MRU3-2 12.00 E

5.3.4

Display of the activation storage

If after an activation the existing current drops again
below the pickup value, e.g. U<, without a trip has
been initiated, LED U< signals that an activation has
occured by flashing fast. The LED keeps flashing until it
is reset again (push button <RESET>). Flashing can be
suppressed when the parameter is set to NOFL.

5.3.5

Parameter set change-over 
switch/external trigger for the
fault recorder

By means of the parameter-change-over switches it is
possible to activate two different parameter sets. Swit-
ching over of the parameter sets can either be done
by means of software or via the external inputs RESET
or blocking input. Alternatively, the external inputs can
be used for Reset or blocking of the triggering of the
fault recorder.

Software-
parameter

Blocking input
used as

RESET input
used as

SET1

Blocking input

RESET input

SET2

Blocking input

RESET input

B_S2

Parameter switch RESET input

R_S2

Blocking input

Parameter
switch

B_FR

Externe Trig-
gerung des Stör-
schreibers

Reset input

R_FR

Blocking input

External trigger-
ing for the fault
recorder

S2_FR

Parameter switch External trigger-

ing for the fault
recorder

With the settings SET1 or SET2 the parameter set is
activated by software. Terminals C8/D8 and D8/E8
are then available as external reset input or blocking
input.

With the setting B_S2 the blocking input (D8, E8) is
used as parameter-set change-over switch. With the
setting R_S2 the reset input (D8, E8) is used as para-
meter-set change-over switch. With the setting B_FR the
fault recorder is activated immediately by using the
blocking input. On the front plate the LED FR will then
light up for the duration of the recording. With the set-
ting R_FR the fault recorder is activated via the reset
input.

With the setting S2_FR parameter set 2 can be activa-
ted via the blocking input and/or the fault recorder via
the reset input.
The relevant function is then activated by applying the
auxiliary voltage to one of the external inputs.

Important note:

When functioning as parameter change over facility,
the external input RESET is not available for resetting.
When using the external input BLOCKING the protec-
tion functions must be deactivated by software block-
ing separately (refer to chapter 5.9.1).

5.4

Protection parameters

5.4.1

1-phase or 3-phase U</U>-
tripping

Switching-over of the parameter permits selection be-
tween 1-phase and 3-phase tripping of the U</U>
steps.
Keys <+> or <-> are used to change the value and
<ENTER> to store it.

Note

When the 

MRU3-2

 is to be used for measuring the re-

sidual voltage in systems with isolated or compensated
neutral or as generator earth fault protection, the
measuring voltage has to be applied to terminals
A3-A4. Undervoltage functions U< and U<< have to
be set to "EXIT" and overvoltage functions U> and U>>
have to be adjusted to the required pickup values.
The frequency must be set to 50 or 60 Hz. The pa-
rameter 1-phase or 3-phase tripping mut be set to
U<>1 (1-phase tripping).

Содержание HighTECH MRU3-2

Страница 1: ...MRU3 2 Voltage relay with evaluation of symmetrical components...

Страница 2: ...e slave address 5 4 7 Setting of Baud rate applies for Modbus Protocol only 5 4 8 Setting of parity applies for Modbus Protocol only 5 5 Parameter for the fault recorder 5 5 1 Adjustment of the fault...

Страница 3: ...nd undervolt age and positive sequence system overvoltage detection in negative and zero se quence system display of measuring values of the line voltages and system voltages U0 U1 and U2 as rms value...

Страница 4: ...Relais 1 Relay 1 Relais 2 Relay 2 Relais 3 Relay 3 Relais 4 Relay 4 L1 L2 L3 t U A B C a b c tU1 tU1 tU2 tU0 U1 U1 U2 U0 A3 A5 A7 A8 Serielle Schnittstelle Serial Interface N G P N G P SELECT RESET EN...

Страница 5: ...ter the supply voltage had been applied 3 1 3 External reset input Refer to chapter 5 9 2 3 1 4 Output relays The MRU3 2 is equipped with 5 output relays Relay 1 C1 D1 E1 and C2 D2 E2 Relay 2 C3 D3 E3...

Страница 6: ...D Flash Suppression of LED flashing after activation P2 FR Parameter switch external trigger for the fault recorder Protection parameters 1 3 1 phase or 3 phase U U tripping U Pickup value for undervo...

Страница 7: ...of the unit The LED marked with FR lights up during parameter setting at the fault recorder When LED lights up date and time are displayed LED PS indicates the phase sequence The 9 LEDs below the SEL...

Страница 8: ...sed by fault induced transients or other system dis turbances The microprocessor continuously compares the measured values with the preset thresholds stored in the parameter memory EEPROM If a fault o...

Страница 9: ...hase has fallen short of the tripping value U Activation cum tripping takes place if all three phases have exceeded the tripping value U Activation cum tripping takes place if one phase has exceeded t...

Страница 10: ...the negative direc tion so called left rotating field consists only of a negative sequence system A measure for the size of the asymmetry of the original system represents the re sidual voltage in the...

Страница 11: ...must be multiplied by 1 3 In this example the sum equals zero Conclusion the source system is symmet rical 4 4 5 System with voltage unbalance Figure 4 4 Graphical determination of the negative sequen...

Страница 12: ...of the shifting results from re placing this system in symmetrical components in the developed zero sequence system Note Shall the relay evaluate the zero sequence system it is absolutely necessary t...

Страница 13: ...RESET one time for each value U tU positive phase sequence system un dervoltage U1 trip delay tU1 Setting value in volt Setting value in seconds SELECT RESET one time for each value U1 tU1 positive p...

Страница 14: ...1 h 12 m 2 s 12 SELECT RESET Software version First part e g D02 Second part e g 6 01 TRIP one time for each part Manual trip TRI TRIP three times Inquire password PSW SELECT RESET ENTER Relay tripped...

Страница 15: ...ltage value can be correctly meas ured between 40 Hz and 70 Hz without adverse ef fects from the frequency With the setting f 50 60 Hz the measured voltage value is influenced by the frequency see Tab...

Страница 16: ...is used as parameter set change over switch With the setting R_S2 the reset input D8 E8 is used as para meter set change over switch With the setting B_FR the fault recorder is activated immediately b...

Страница 17: ...al under over voltage settings Both elements can be blocked or set as alarm stages 5 4 4 Negative sequence system overvoltage U2 This parameter determines the treshold for the rms value of the negativ...

Страница 18: ...a trip has occured A_PI After Pickup Storage is initiated after the last activation threshold was fallen short of TEST Storing is activated by simultaneous actuation of the keys and During the recordi...

Страница 19: ...SELECT RESET the display switches cyclically to the next value After the measuring values had been indicated the setting pa rameters are displayed Hereby the LEDs in the upper section signalize which...

Страница 20: ...any case the assignment has to be met which phase sequence shall correspond to the positive sequence system Display 123 means that the connected rotating field has the positive sequence system of uni...

Страница 21: ...s shown By pressing SELECT RESET the fault measuring values can be scrolled By pressing it can be scrolled back to a more recent fault data set At first FLT8 FLT7 are al ways displayed When fault reco...

Страница 22: ...in the assignment mode The assignment mode can be reached only via the blocking mode By pressing push button SELECT RESET in blocking mode again the assignment mode is selected The relays are assigne...

Страница 23: ...the parameters are not affected 5 9 3 Erasure of fault storage To delete the trip store the push button combination SELECT RESET and has to be pressed for about 3s The display shows wait Relay functio...

Страница 24: ...he circuit breaker if tripping is not desired By pressing the push button TRIP once the display shows the first part of the software version of the relay e g D08 By pressing the push button TRIP twice...

Страница 25: ...u lation Voltage adjustable from 0 to 2 x UN Timer to measure the operating time Accuracy class 10 ms Switching device Test leads and tools 6 4 1 Example of the test circuit For testing of the MRU3 2...

Страница 26: ...and the theoretical value accept to the table Symmetrical measuring voltage system For this test the relay has to be correctly connected with all of the three phases and the star point If the measuri...

Страница 27: ...function or smaller than 1 03 for undervoltage 6 4 5 Checking the relay operating time of the over undervoltage functions To check the relay s operating time a timer must be connected to the trip outp...

Страница 28: ...he relay works and measures correctly 6 6 Maintenance Maintenance testing is generally done on site at regu lar intervals These intervals vary among users depend ing on many factors e g the type of pr...

Страница 29: ...error class index E 10 ms Minimum operating time 40 ms Max allowed interruption of the auxiliarxy supply without effecting the function of the device 50 ms Weight approx 1 5 kg Mounting position any I...

Страница 30: ...800 V EXIT 0 04 50 s EXIT 1 V 1 V 2 V 0 01 0 02 0 05 0 1 0 2 0 5 1 0 2 0 s 1 of set value or 0 3 UN 1 oder 15 ms U U U U1 tU tU1 tU1 UN 100 V 2 200 V EXIT UN 230 V 2 460 V EXIT UN 400 V 4 800 V EXIT 0...

Страница 31: ...x 8 s 3 4 x 4 s 7 8 x 2 s 50 Hz 1 2 x 6 66 s 3 4 x 6 66 s 7 8 x 1 66 s 60 Hz FR Savings of the recording at the occurence P_UP TRIP A_PI TEST FR Pre trigger time 0 05 s 8 00 s is written over when a...

Страница 32: ...asuring of the positive phase sequence negative phase sequence and zero phase sequence system component 1 2 Rated voltage 100 V 230 V 400 V 1 2 4 Housing 12TE 19 rack Flash mounting A D RS 485 Alterna...

Страница 33: ...lue for undervoltage element V 80 190 320 tU Tripping delay for undervoltage element s 0 04 U Pickup value for overvoltage element V 110 250 440 tU Tripping delay for overvoltage element s 0 04 U Pick...

Страница 34: ...king function Default setting Actuala setting Blocking Not blocking Blocking Not blocking Parameter set Set 1 Set 2 Set 1 Set 2 Set 1 Set 2 Set 1 Set 2 U X X U X X U X X U X X U1 X X U1 X X U2 X X U0...

Страница 35: ...lugged Not plugged X No function X Code jumper Low High range for reset input Low High range for blockage input Default settings Actual settings Werkseinstellung Eigene Einstellung Low plugged X X Hig...