18
TB MRI3-ITE(R) 12.00 E
5.1.1
LEDs
LED-Name
Mode
Colour
LED-Display
Meaning
L1, L2, L3, E
Display of measuring
values
green
continuously
Current measuring
(phase or earth current)
ϑ
A
and
ϑ
T
Display of measuring
values
yellow
continuously
Measuring of the temperature
equivalent (%)
L1, L2, L3, E
Pickup
red
flashing
Overcurrent pickup
(phase or earth current)
IP, IQ*
Display of measuring
values
yellow
continuously
Wirk- und Blindstromanteil f. Erd-
strom
ϑ
A
and
ϑ
T
Pickup
yellow
flashing
Base current exceeded (I
B
*k)
ϑ
A
and
ϑ
T
*
Pickup
green
flashing
Base current exceeded (I
B
*k)
ϑ
A
and
ϑ
T
*
Pickup
red
flashing
Base current exceeded (I
B
*k)
L1, L2, L3, E,
(I
>
, I
>>
, I
E>
, I
E>>
)
After pickup
green
flashing (short)
Pickup signalized (In combination
with trip element only)
L1, L2, L3, E
Tripping
red
continuously
Overcurrent tripping
(phase or earth current)
L1, L2, L3, E,
ϑ
A
and
ϑ
T
(I
B,A
, I
B,T
)
After pickup
yellow
flashing (short)
Pickup signalized (In combination
with trip element only)
ϑ
A
Warning at k
2
⋅
100%
yellow
continuously
Temperature limit of overload low set
element reached
ϑ
T
Tripping at k
2
⋅
100%
yellow
continuously
Temperature limit of trip element
reached
ϑ
A
*
Warning at k
2
⋅
100%
yellow
continuously
Temperature limit of overload low set
element reached
ϑ
T
*
Tripping at k
2
⋅
100%
yellow
continuously
Temperature limit of trip element
reached
I
B,A
Setting
green
continuously
Setting switch point
k
A
Setting
red
continuously
Define constant
I
B,A
(
ϑ
A
)
Pickup
green
flashing
Base current exceeded (I
B,A
*k)
I
B,A
(
ϑ
A
)
Tripping
red
flashing
Temperature limit of overload low set
element reached
I
B,T
Setting
green
continuously
Setting switching point
k
T
Setting
red
continuously
Define constant
I
B,A
(
ϑ
T
)
Pickup
red
flashing
Base current exceeded (I
B,T
*k)
I
B,T
(
ϑ
T
)
Tripping
red
continuously
Temperature limit of trip element
reached
τ
C
Setting
green
continuously
Cooling time constant
τ
W
Setting
red
continuously
Warming up constant
I>
Setting
green
continuously
Setting switching point I>
CHAR I>
Setting
green
continuously
Select characteristic
t
I>
Setting
red
continuously
Setting time delay t
I>
t
I>
, CHAR I>
Setting
red/green
continuously
Reset mode activating
I>, t
I>
Pickup
red
flashing
Pickup of I>
I>, t
I>
Tripping
red
continuously
I> tripped
I>>
Setting
green
continuously
Setting switching point I>>
t
I>>
Setting
red
continuously
Setting time delay t
I>>
I>>, t
I>>
Pickup
red
flashing
Pickup of I>>
I>>, t
I>>
Tripping
red
continuously
I>> tripped
I
E>
Setting
green
continuously
Setting switching point I>
CHAR I
E>
**
Setting
green
continuously
Select characteristic
t
IE>
Setting
red
continuously
Setting time delay t
IE>
t
IE>
, CHAR I
E
**
Setting
red/green
continuously
Reset mode activating
→←
*
Setting/tripping
red
continuously
Directional feature for earth current
I
E>
, t
IE>
Pickup
red
flashing
Pickup of I
E>
I
E>
, t
IE>
Tripping
red
continuously
I
E>
tripped
I
E>>
Setting
green
continuously
Setting switching point I
E>>
t
IE>>
Setting
red
continuously
Setting time delay t
IE>>
I
E>>
, t
IE>>
Pickup
red
flashing
Pickup of I
E>>
I
E>>
, t
IE>>
Tripping
red
continuously
I
E>>
, tripped
RS
Setting
yellow
continuously
Setting slave address
Table 5.2: LED-indication
*
MRI3-ITER
type only
**only
MRI3-ITE
type