TB MRI3-ITE(R) 12.00 E
35
7.3.2
Time overcurrent protection and thermal replica
Setting range
Step
Tolerance
I
B,Alarm
0.4...3.5 x I
N
(EXIT)
0.02 x I
N
(0.4...1.0)
0.05 x I
N
(1.0...3.5)
±
3% from set value
or
±
2.5% I
N
k
A
0.5...5
0.01 (0.5...1.0)
0.02 (1.0...2.0)
0.05 (2.0...5.0)
I
B,TRIP
0.4...3.5 x I
N
(EXIT)
0.02 x I
N
(0.4...1.0)
0.05 x I
N
(1.0...3.5)
±
3% from set value
or
±
2.5% I
N
k
T
0.5...5
0.01 (0.5...1.0)
0.02 (1.0...2.0)
0.05 (2.0...5.0)
τ
W
0.5...180 min
0.1 (0.5...2) min
0.2 (2...5) min
0.5 (5...10) min
1 (10...20) min
2 (20...50) min
5 (50...100) min
10 (100...180) min
τ
C
0.5...180 min
0.1 (0.5...2) min
0.2 (2...5) min
0.5 (5...10) min
1 (10...20) min
2 (20...50) min
5 (50...100) min
10 (100...180) min
I>
0.2...4.0 x I
N
(EXIT)
0.01 (0.2...0.5)
0.02 (0.5...1.0)
0.05 (1.0...2.0)
0.1 (2.0...4.0)
±
3% from set value
t
I>
0.04 - 260 s (EXIT)
(definite time)
0.05 - 20 (EXIT)
(inverse time)
0.02 (0.04...1.0)
0.05 (1.0...2.0)
0.1 (2.0...5.0)
0.2 (5.0...8.5)
0.5 (8.5...10.0)
1.0 (10...20)
2.0 (20...50)
5.0 (50...100)
10.0 (100...260)
0.01 (0.05...0.5)
0.02 (0.5...1.0)
0.05 (1.0...2.0)
0.1 (2.0...5.0)
0.2 (5.0...10.0)
0.5 (10.0...20.0)
±
3% or
±
20 ms
±
5% for NINV
and VINV
±
7,5% for NINV
and EINV
I>>
0.5...40 x I
N
(EXIT)
0.05 (1.0...2.0)
0.1 (2.0...4.0)
0.2 (4.0...10.0)
0.5 (10.0...20.0)
1.0 (20.0...40.0)
±
3% from set value
t
I>>
0.04...10 s (EXIT)
0.02 (0.04...0.5)
0.05 (0.5...2.0)
0.1
(2.0...5.0)
0.2
(5.0...10)
±
3% or
±
20 ms
Table 7.1: Setting values and steps