Sequencer COMPACT
Technical brochure
FI 72.0467.0118E
Page 33 / 42
Page Parameters of the Pressure Switch
1: Maxi dP threshold. If the dP measure exceeds the threshold more than one second, declogging dP order becomes
« present ».
Adjustments form 0 to 500 daPa (setting enabled in level 1 & 2).
2: Mini dP threshold. If the dP measure falls below
the threshold, declogging dP order becomes « absent ».
Adjustments from 0 to 500 daPa (setting enabled in level 1 & 2)
Note: if Maxi dP= Mini dP=0 then dP order is forced to « present ».
3: T2A threshold: accelerated running threshold. Adjustments from 0 to 500 daPa (setting enabled in level 1 & 2)
If dP measure exceeds this threshold more than 5 seconds
→
accelerated running
→
T2 = T2A
If dP measure falls below this threshold more than 5 seconds
→
normal running
Note: if the threshold is adjusted at 000, the function is inactive (always in normal running).
4: High Alarm dP threshold. Adjustments from 0 to 500 daPa (setting enabled in level 1 & 2)
If dP measure exceeds this threshold more than 5 seconds
→
High Alarm dP
If dP measure falls below this threshold more than 5 seconds
→
No High Alarm dP
Note: if the threshold is adjusted at 000, the function is inactive (no High Alarm dP).
5: Low Alarm dP threshold. Adjustments from 0 to 500 daPa (setting enabled in level 1 & 2)
If dP measure exceeds this threshold more than 5 seconds
→
Low Alarm dP
If dP measure falls below this threshold more than 5 seconds
→
No Low Alarm dP
Note: if the threshold is adjusted at 000, the function is inactive (no Low Alarm dP).
6: Adjustment of the zero pressure when area is pressed and validated. (setting enabled in level 2)
Before this, the device must be switched off by disconnecting the 2 pressure plugs.
Display of the instantaneous dP measure
7: Setting of the sample rate of the recording. (setting enabled in level 1 & 2)
Adjustment from 1 to 60 sec.
8: Link towards main page / synoptic
9: Link towards page parameters
1
2
3
4
5
6
8
9
7