DIFFERENTIAL PRESSURE SWITCH

 

 
 

 

 

Technical Notice

 

  FI 72.0226.1016E 

 

Page 9 sur 10 

 

 

General instructions for safety, assembly, commissioning, usage and maintenance 

to be read before working on the device 

I. GENERAL 
These instructions must be read jointly with: 
+the standard NFC15-100 
+the technical data sheet specific to the device 
The  Sefram  devices  are  designed  to  be  assembled, 
commissioned  and  used  in  compliance  with  the 
characteristics/data  given  in  the  technical  data  sheet. 
Always  adhere  to  all  of  directives,  legislation,  orders 
and most recent standards in force for the stated field of 
application. 
The assembly, commissioning, usage and maintenance 
operations must  always  be  carried  out  by  qualified  and 
authorised personnel.  
Personnel working on the devices must be familiar with 
the safety rules and requirements in force regarding the 
components, 

devices, 

machines 

and 

electrical 

installations. 
II. RECEPTION - STORAGE 
After unpacking the device, check that this latter has not 
been  damaged  during  transport;  for  certain  devices, 
remove the protective film from the cover. The material 
must be stored inside in a dry place. 
In the event of a problem, please contact Sefram. 
III. ASSEMBLY  
The  assembly  operations  must  be  carried  out  by 
qualified,  skilled  and  authorised  personnel.    Personnel 
working  on  these  devices  must  be  familiar  with  the 
safety rules and requirements in force.   
The box must be mounted vertically. 
For  material  connected  permanently  to  the  network,  a 
quickly  accessible  cut-off  device  must  be  incorporated 
into the cabling installation of the building. 
The  device  supply  must  be  equipped  with  a  device  for 
protection  against  risks  of  over-current  and  fault 
isolation.    The  number  of  poles  protected  must  be 
appropriate to the neutral regime of the building and to 
the regulations in force. 
The equipment must be connected to the PE protection 
mass by green/yellow wires (NFC15-100). 
The  device  is  compatible  with  the  neutral  regimes  TT, 
TN or IT; 
Nevertheless,  we  recommend  that  the  device  is 
supplied  through  the  intermediary  of  an  insulation 
transformer  for  which  the  primary  is  supplied  between 
phases  and  not  between  phase  and  neutral,  so  as  to 
avoid  any  accidental  over-voltage  caused  when  the 
neutral is cut before the phases.  
In the event of a problem, please contact Sefram.

 

IV. COMMISSIONING AND USAGE 
Commissioning 

is 

authorised 

only 

after 

duly 

establishing  that  the  device,  the  machine  or  the 
installation in which the device has been integrated in a 
compliant  manner,  satisfies  all  of  the  directives, 
legislation, orders and most recent standards in force.  
Commissioning  operations  must  be  carried  out  by 
qualified,  skilled  and  authorised  personnel.  Personnel 
working  on  these  devices  must  be  familiar  with  the 
safety rules and requirements in force.  
Note:  correct  operational  functioning  does  not  in  itself 
constitute 

an 

indication 

of 

conformity 

to 

the 

recommendations  for  the  use  of  the  material  in 
complete safety.   
Also  read  the  maintenance  recommendations  which 
equally apply during commissioning and use.  
In the event of a problem, please contact Sefram 
V. MAINTENANCE 
The device does not require any special maintenance. 
For  devices  equipped  with  the  pressure  measurement, 
in  order  to  retain  a  precise  pressure  measurement,  an 
annual  calibration  is  advised  particularly  at  « zero » 
(see § calibration on the technical data sheet) 
The following operations are recommended; they 
constitute a minimum: 

Before  any  work  intervention,  we  recommend 
that  the  dust  is  removed  before  opening  the 
box, 

The  MDPP2S-V2  uses  double  pole  neutral 
fusing.  Power-off  the  system  and  replace  both 
fuses with appropriate replacement fuses. 

The  device  must  not  be  opened  in  an 
excessively dusty environment, 

The settings must be carried out in the shortest 
lapse of time so as not to engender any risks, 

The  integrity  of  the  joints  must  be  checked: 
remove any trace of dust or other deposit, 

Remove  any  trace  of  dust  which  could  have 
penetrated during the setting operation, 

Always  ensure  that  the  transparent  cover  is 
correctly closed. 

 

Maintenance  operations  must  be  carried  out  by 
qualified,  skilled  and  authorised  personnel.    Personnel 
working  on  these  devices  must  be  familiar  with  the 
safety rules and requirements in force.  
In the event of a problem or any questions during these 
operations please contact SEFRAM. 
 

ATEX  version  :  See  FI  72.0172  or  FI  72.0341 
instructions 

Содержание MDPP 2000

Страница 1: ...DIFFERENTIAL PRESSURE SWITCH Technical Notice FI 72 0226 1016E Page 1 sur 10 Version MDPP2S V2...

Страница 2: ...cs 1 x NO NC 1A 250V AC1 To be protected by the user Remote interfacing 4 20mA output integrated supply maxi load 500 Ohms Scale measure 6 00 Bars Proof pressure 300 PSI 20 Bars Burst pressure 450 PSI...

Страница 3: ...essure measurement is displayed on a 3 digit super bright led display Its running suits to supervision of a compressed air network intended to filters declogging The devise includes two relays It can...

Страница 4: ...an Xk1 threshold Xk1 relay is supplied contact between 11 and 14 and Xk1 red led is switched off If the pressure is lower than Xk1 threshold the relay is no longer supplied contact between 11 and 12 a...

Страница 5: ...s the SELECT key loosen keys the zero is adjusted ADJUSTMENT The device leaves our workshops the scale pressure in order from zero to full scale Adjustments Made after stabilisation and at 20 C INSTAL...

Страница 6: ...calibre T160mA for a 115VAC supply voltage T80mA for a supply voltage in 230VAC or T500mA for a supply voltage in 24VDC Fix the MDPP2Sv2 in vertical position Avoid the input of dust air at pressure co...

Страница 7: ...ICAL CONNECTIONS Bottom card user connections To access to this card remove the connections cover of the box According to device configuration some parts can be not provided At rest out of voltage con...

Страница 8: ...DIFFERENTIAL PRESSURE SWITCH Technical Notice FI 72 0226 1016E Page 8 sur 10 SPACE FIXING...

Страница 9: ...primary is supplied between phases and not between phase and neutral so as to avoid any accidental over voltage caused when the neutral is cut before the phases In the event of a problem please conta...

Страница 10: ...device is forbidden You must send us back the device in our workshops otherwise the certification and the guarantee are lost In case of failure no action is permitted and the unit must be returned to...

Отзывы: