DIFFERENTIAL PRESSURE SWITCH
Technical Notice
FI 72.0226.1016E
Page 6 sur 10
PRECAUTIONS:
-
In version AC: The MDPP2Sv2 leaves our workshops with jump position for using in 230VAC (except if
specified at the order). Check jump position according to supply voltage:
-
If you have to change fuse, replace it by the same calibre: T160mA for a 115VAC supply voltage, T80mA
for a supply voltage in 230VAC or T500mA for a supply voltage in 24VDC.
-
Fix the MDPP2Sv2 in vertical position.
-
Avoid the input of dust air at pressure connections.
-
Take care about device characteristics (humidity, maxi pressure, etc.).
-
Don’t remove the MDPP2Sv2 front panel in order to connect (only connections cover)
-
To connect the 4-20mA, it’s advised to use some shielded cable and not to follow power cables.
-
Interventions must always be realised by a skilled staff.