ELECTRICAL REQUIREMENTS

INSTALLING THE MAINS POWER CABLE

The power cable, included with your cooler will have boot lace 

ends ready for connection to the mains power supply.
Means for all pole disconnection must be incorporated in the 

fixed wiring in accordance with the wiring rules.

Field Wiring

Pass the power cable through the conduit gland located on 

corner of unit.

Terminate the power cable in a junction box installed nearby. 

Refer to the field wiring diagram below. The fixed wiring must 

be fitted with an all pole disconnection switch that breaks the 

active and neutral in accordance with local wiring rules. We 

recommend the junction box be located and installed on the 

dropper. 

WARNING! 

Do not let the cable, the cable ends, or the control 

box get wet. 

ILL2149-A

GROMMET 

CONTROLLER

CABLE

POWER

INSTALLING THE CONTROLLER CABLE

Seeley International recommends:

• 

Not routing data/communication and supply mains voltage 

cables in the same conduit.

• 

Not cable tying or taping data/communication and supply 

mains voltage cables together.

• 

A minimum separation distance, as specified by your 

local wiring standards, between data/communication and 

supply mains cables. In Australia, this minimum separation 

distance is 50mm .

Connect one end of the control cable (with ferrite suppressor) to 

the cooler electronics box. The wall control cable can be fitted 

to either of the RJ ports

Down Discharge Units

A hole is provided in the side of the blower housing for control 

cable entry. The control cable can be passed through this hole 

and wired to the control box. On installation pass the cables 

through the hole into the dropper and then into the roof cavity

Side & Top Discharge

Using knockout located on the corner pillar on the opposite side 

to the mains connection
Feed looped end of the controller cable through the supplied 

grommet then fit the grommet into hole left after knock out was 

removed. 

Note! 

It is important to route the control and power cables out 

through included grommets / conduit. 

Note!

 The maximum length for the wall control cable to travel 

alongside the power cable is 10m

.

WARNING! 

Do not let the cable, the cable ends, or the control 

box get wet. 

IMPORTANT REMINDER! 

Do not route extra-low voltage data/communication and low 

voltage supply mains cables without first consulting your local 

wiring standards. Routing data/communication cables and 

supply mains cables in close proximity can present an electrical 

hazard and can be detrimental to the performance of the 

product, resulting in intermittent communication errors, locking 

up of screens, displays dropping out and inconsistent erratic 

operation.

It is required that all units be connected to the mains supply 

through an independent circuit, suitably protected by fuse or 

circuit breaker. Ensure that the power supply is sufficient for the 

rating indicated on the serial plate. Wire the unit in accordance 

with all state and local regulations.

NOTE
An all pole disconnection switch must be incorporated in the 

fixed wiring in the accordance with the wiring rules.

ILL3005

ILL2149-A

ILL3006

Содержание Braemar RPCQi Series

Страница 1: ... English INSTALLATION MANUAL RPCQi Evaporative Coolers Original English Instructions ON ON OFF OFF COOL SPEED INTERNA TIONAL AIR ...

Страница 2: ...CTING THE MAGIQTOUCH MAGIQCOOL CONTROLLER OR SWITCH PLATE 6 MagiQcool Wall Control Displays Service 6 COMMISSIONING THE COOLER 7 Diagnostic Led 7 Salinity Led 7 Magiqtouch Controller Information 7 FAULT CODES 8 TESTING THE DIRECT DRIVE MOTOR 8 CHANGING THE WATER MANAGEMENT METHOD FOR THE MAGIQCOOL CONTROL 8 SETTING THE WATER LEVEL 9 TESTING THE DRAIN VALVE 9 REFITTING THE PAD FRAMES 9 TESTING THE ...

Страница 3: ...CONTRACTORS RISK ASSESSMENT A risk assessment of all hazardous tasks is required under legislation A risk assessment is an essential element that should be conducted before the commencement of work to identify and eliminate the risk of falls or to minimise these risks by implementing control measures There is no need for this to be a complicated process it just is a matter of looking at the job to...

Страница 4: ... around the cooler for maintenance Provision must be made for access to electricity water supplies and drains RPCQi MODELS ILL1646 A Note Do you need to discuss the installation of items like safety anchor points with the customer PREPARING THE DROPPER IF REQUIRED LEVELLING THE DROPPER Ensure the top of the dropper is level and square in all directions use a spirit level This helps with levelling ...

Страница 5: ...y removing the pad frames first They can be replaced at the very end of the installation procedure Do not slide the cooler lift and carry it It is recommended that at least 2 people carry the cooler whenever it needs to be moved Do not drop the cooler Always handle with care Important For lifting or pulling purposes when using ropes or slings always apply the ropes around fan housing Never tie the...

Страница 6: ... of the blower housing for control cable entry The control cable can be passed through this hole and wired to the control box On installation pass the cables through the hole into the dropper and then into the roof cavity Side Top Discharge Using knockout located on the corner pillar on the opposite side to the mains connection Feed looped end of the controller cable through the supplied grommet t...

Страница 7: ... H K L WATER SUPPLY Mains connection is made to the float valve fitted in the reservoir The float valve must be set to maintain the reservoir water level about 10 mm below the overflow level The mains water supply should be fitted with a ball valve and connection to the unit from the stopcock be made with the appropriate copper pipe and fittings NOTE Flush the mains supply before connection to the...

Страница 8: ...ximum cable length allowed from the MagIQtouch controller to the first cooler is 25 metres 82 For any additional coolers added into the system with a link module the maximum allowed length is 40 metres 131 Therefore failure of the product or components to operate correctly due to modification to supplied cables or the use of non approved cables will NOT be accepted under the Manufacturer s Warrant...

Страница 9: ...nostic indicator If the top LED is double flashing green everything is OK this is normal operation SALINITY LED The bottom LED is red only and displays salinity setting information COMMISSIONING THE COOLER Sal Flash Controller Salinity Setting 5 Flash Salinity Control set 5 Flash Timed Drain 4 Flash The Salinity Control method is set for continuous bleed bleed tray used 5 Flash Thermostatic Contro...

Страница 10: ... then this fault will be indicated Petrol generators are the most likely cause of this type of fault This typically will not occur on mains power supplies FAULT CODES EXTRA NOTES FOR THE MAGIQTOUCH CONTROLLER ONLY Fault Code 07 7 Red Flashes Motor Error MagIQtouch Controller Only LED Indicates Hall Effect ON Normal operation OFF One or more Hall effects sensors in motor not detected Thermal O L ON...

Страница 11: ...o set height K J I H H Overflow I Tank J Plastic Nut K Threaded Bush L O Ring Between H K 10 5 L TESTING THE DRAIN VALVE REFITTING THE PAD FRAMES Refit the pad frames to unit Ensure all pads have been correctly fitted before attaching and tightening the pad retaining locking strips with a philip head screwdriver With the wall control in OFF mode press and hold the and buttons together for 1 second...

Страница 12: ... for the first 10 seconds each time it starts up It will then return to the set fan speed Prewet When COOL mode is activated the pump will run for 90 seconds before the fan is switched on Salinity Level Sets the salinity level at which the tank will drain in SALINITY MEASUREMENT mode Tank Drain Delay Sets the time delay before the drain valve opens after the pump in the cooler is turned off AutoCl...

Страница 13: ... The water pipes were flushed of any foreign materials before connection to cooler was made NO EXTERNAL LEAKS The water is connected with no leaks at fittings NO INTERNAL LEAKS Check all internal water hoses are securely fitted to water distribution spreaders and other internal fittings SECURE Water pipes are correctly saddled as per plumbing regulations OWNER INSTRUCTIONS The owner has been instr...

Страница 14: ...ntroller failure Replace MagIQtouch Controller Pump runs but no water circulation Pump runs but pads lack water Insufficient water in tank Adjust float level Water hoses blocked Check and clean out blockage Pump strainer blocked Clean pump strainer Insufficient water supply pressure Check and confirm water supply pressure Water solenoid is installed incorrectly Check installed in the correct water...

Страница 15: ...BRAEMAR RPCQi EVAPORATIVE COOLERS INSTALLATION MANUAL 13 ...

Страница 16: ...del selected RPCQi Cooler Installation Manual Now provided on the internet Refer www seeleyinternational com For Australia Only Seeley International Technical Support 1300 650 399 Seeley Spare parts Distributors 1300 367 437 Authorised Service Agents 1300 650 644 Service All regions other than Australia Please contact your local distributor seeleyinternational com Manufactured by Seeley Internatio...