49
Configuration
Command Menu-->Panel Config-->Features
3. Aux Dis Corr
[X] ENABLE ->Default
[ ] DISABLE
By default this function will
disconnect the auxiliary alarm
relay when the aux disconnect
button is pressed. If enabled,
this function will disconnect
the auxiliary alarm relay
and
all correlated relays when the
aux disconnect button is
pressed.
Correlated relays
include: MR-2306-R6 and
MR-2312-S12.
Command Menu-->Panel Config-->Features
4. Sig-Sil Inh Tmr
[X] DISABLE->Default
[ ] 10sec
[ ] 20sec
[ ] 30sec
[ ] 1min
Use this function to inhibit the
signal silence switch for a
desired length of time. The
time period should expire
before the signals may be
silenced. According to the
Canadian National Building
Code, this timer should be set
to one minute.
Command Menu-->Panel Config-->Features
5. Aux. Dis. Dis Alam&Sv
[ ] ENABLE
[X] DISABLE->Default
If enabled the Common Alarm
and Common Supervisory
relays will be disconnected
when Aux. Disconnect is
pressed. Also, the MR-2300-
PR will not transmit a
supervisory or alarm event. If
disabled, the Aux disconnect
switch has no effect on the
Common Alarm relay, the
Common Supervisory relay,
and the MR-2300-PR.
Command Menu-->Panel Config-->Features
6. Auto Sig-Sil. Tmr
[X] DISABLE->Default
[ ] 5 Min
[ ] 10 Min
[ ] 20 Min
[ ] 30 Min
Use this function to set the
time period for which the
indicating circuits will sound
before they are automatically
silenced. For UL installations,
disable the Auto Signal
Silence Timer.
Command Menu-->Panel Config-->Features
7. Rem. Annun.
[X] NONE->Default
[ ] 1
[ ] 2
...
[ ] 6
Use this function to program
the number of remote
annunciators. Any combination
of remote annunciators or
smart relays can be used as
long as the number does not
exceed 6. The annunciators’
addresses should be linear:
without gaps and in sequence.
Command Menu-->Panel Config-->Features
8. Alarm Xmit-Sil.
[ ] ENABLE
[X] DISABLE->Default
Use this function to allow the
alarm transmit and auxiliary
alarm relay to reset on the
Signal Silence rather than the
Reset switch.
Aux Dis. Dis Corr
[X] ENABLE
Sig-Sil. Inhibit Timer
[X] DISABLE
Aux Dis. Dis Alm&Sv
[X] DISABLE
Auto Sig-Sil. Tmr
[X] DISABLE
No. of Remote Annun.
[X] NONE
Alm Xmit-Sil.
[X] DISABLE