background image

11 

of 12

10 

of 12

Test 1 – Verifying 

correct startup 

The DEM680E should be calibrated with 

a non-zero nuisance delay setting. 

With the door closed

, the LED should be GREEN, 

indicating that it is active (see 

Diagram 36

). 

•  If the LED is RED or AMBER, stop and consult 

the 

Troubleshooting Guide

 to correct.

Test 2 – Verifying 

door security

With the door closed

, PUSH against the face of 

the door WITHOUT releasing the primary locking 

mechanism (e.g., an exit device or cylindrical/mortise 

door lock). The nuisance alarm should not sound if 

the door is adjusted properly (see 

Diagram 37

).

• If the nuisance alarm sounds

, there is too much door 

movement. The primary locking mechanism must be 

adjusted to reduce excessive door travel. Excessive 

movement will cause the DEM680E to go into alarm 

and unlock when the door is pulled from the unsecure 

side. Make necessary corrections and repeat Test 2.  

Test 3 – Verify nuisance 

alarm function 

UNLOCK the primary locking mechanism (push bar or turn 

handle) and attempt to push the door open. The nuisance 

alarm should sound (see 

Diagram 38

). Close the door before 

the nuisance interval expires to prevent the alarm state.

• If the nuisance alarm does not sound

, the strike 

assembly screw may have been overtightened. 

Overtightening prevents the door from traveling past 

the nuisance threshold. Refer to “No Alarm” in the 

Troubleshooting Guide

 and 

Diagram 14

 which shows 

proper adjustment of the strike assembly screw. 

Test 4 – Verify countdown 

alarm & free egress 

UNLOCK the primary locking mechanism and attempt to 

open the door. The nuisance alarm should sound along 

with a flashing strobe. Maintain pressure on the door 

until the alarm becomes steady; the DEM680E is now in 

alarm state. The door should open in 15 or 30 seconds, 

depending on the exit and nuisance delay settings. At 

the end of the alarm interval, the LED should turn red, 

and the door should freely open. (see 

Diagram 39

).

*After testing, close the door and perform a reset. After 

reset, the strobe should turn off and the LED should change 

from red to green. VERIFICATION IS COMPLETE.

MAGNALOCK OPERATIONAL TESTS

Troubleshooting Guide

TROUBLE INDICATOR

POSSIBLE CAUSES

POSSIBLE SOLUTIONS

Solid RED

•  Two bond sensor failures*
•  Supply voltage < 8.5 VDC
•  Two bond sensor failures* 

•  Ensure bond sensor connectors are properly seated 
•  Check power supply voltage
•  Ensure bond connectors are properly seated

Solid RED with 

Audible Alarm

•  Open door
•  DPS failure*
•  Attempting to calibrate with two bond sensor failures*
•  Strike tray installed upside down
•  DPS magnet missing from strike tray

•  Close door
•  Ensure DPS connector is properly seated
•  Ensure bond connectors are properly seated
•  Ensure that the strike tray is mounted 

with alignment tabs facing up

•  Check strike tray for damage, replace if needed

Solid AMBER

•  Door sag 
•  Obstructed strike/magnet face
•  Supply voltage < 10.8 VDC
•  Single bond sensor failure*
•  Magnet disconnected or magnet cable wire broken
•  Verify that the strike label has been removed

•  Recalibrate
•  Check for obstructions between strike and magnet
•  Clean face of strike and magnet. Recalibrate
•  Check power supply voltage
•  Ensure bond connectors are properly seated
•  Make sure magnet connector is properly 

seated or repair magnet cable wire

Flashing RED

•  Factory reset

•  Ensure SW10 is in the OFF position

LED off

•  LED disabled by SW1
•  Supply voltage < 5 VDC

•  Turn SW1 to the ON position
•  Check power supply

Intermittent alarm

•  Over-tightened strike screw

•  Unscrew strike screw 1/2 turn at a time 

until alarm sound is constant when door 

is pushed (Recalibrate lock after each 

adjustment and repeat 

Install Verification

)

No alarm

*  Failure means that the circut cannot detect a signal from the sensor. Check that the sensor connectors are properly 

seated and inspect sensor wires for damage. Call Technical Support if replacement is needed.

Diagram 36  Indicator light displays

Diagram 37  

Diagram 39 

Diagram 38

Содержание ASSA ABLOY Magnalock DEM680E Series

Страница 1: ...ns Dimensions Height 2 50 64 mm Depth 2 56 65 mm Length 11 50 292 mm Certifications UL 10C Fire Rated 1 Hour CAN ULC S104 Fire Door Conformant UL 294 UL Tested Ratings Endurance 100 000 cycles ANSI BH...

Страница 2: ...needed on one or both sides of the bracket see Diagram 9 4 REMOVE the protective tape from the frame 5 Temporarily INSTALL the mounting bracket with template pins against the closed door using a Phill...

Страница 3: ...IGHTEN the screw into the sex bolt using the 3 16 hex wrench While tightening gently tap the head of the sex bolt using a rubber mallet until the head sits flush with the door NOTE To provide maximum...

Страница 4: ...dooropens Normally open 2 3 Normally closed NC Normallyclosedcircuit openswhendooropens JP3 EXT INIT 1 2 Disabled Whenenabled allowsunitto beinitiatedfromanexternal source J1 Terminal4 Disabled 2 3 En...

Страница 5: ...PERFORM amanualcalibrationimmediately followinginstallation ifnecessary 1 ENSURE that the door is closed 2 APPLY power to the Magnalock 3 PRESS AND RELEASE the calibration button see Diagram 34 4 VER...

Страница 6: ...ld turn red and the door should freely open see Diagram 39 After testing close the door and perform a reset After reset the strobe should turn off and the LED should change from red to green VERIFICAT...

Страница 7: ...E Each DEM680E comes with an NFPA exit delay door label as required by fire code 1 FOLLOW the included application instructions to apply the lettering to a door Restoring factory defaultsettings 1 DIS...

Отзывы: