AQD5 12v/24v Series Power Supply continued 

AQD5 Series Instructions:  Doc.#500-33005 Rev.A  

Page 3 of 4 

 

Maintenance 

The power supply and stand by battery(s) should be tested at least once a year as follows: 

1.  Check LED’s for normal state.  AC ON Green, Trouble Normal ON Green, DC ON Red. 
2.  Check output voltage with normal load.  For 12v setting, voltage should read between 13.60 and 13.80vdc and 

27.1 and 27.6vdc on the 24v setting.  This assures proper voltage to float charge batteries. 

3.  Disconnect AC input.  AC LED should be off, all other LED’s should remain normal. 
4.  Check DC Output to be above 12.0vdc for 12v setting and 24.0vdc for 24v setting.  This checks standby 

batteries to be operational.  Sealed lead acid batteries have a typical life of 3 to 5 years. 

5.  Re Apply AC and verify AC LED ON. 
 

Battery Selection 

The table below shows typical standby time in hours for various loads and batteries.  The table works for either 12vdc 
or 24vdc.  The AQD5 was evaluated at UL with a 7AH sealed lead acid battery with a 1 hour stand by. 
 

Approximate Battery Standby Time Table with a reserve of 3 Amps for 5 minutes for Alarm  

Total Output 

Amps 

4Ah Battery 

Standby 

7Ah Battery 

Standby 

12Ah Battery 

Standby 

24Ah 

Standby 

40Ah 

Standby 

.5A 

5.5 Hrs 

12 Hrs 

20 Hrs 

40 Hrs 

65 Hrs 

1A 

2.5 Hrs 

5 Hrs 

9 Hrs 

19 Hrs 

32 Hrs 

1.3A 

2 Hrs 

4 Hrs 

7.2 Hrs 

15.5 Hrs 

24 Hrs 

2A 

1 Hrs 

2 Hrs 

5 Hrs 

10 Hrs 

15 Hrs 

3A 

.5 Hrs 

1 Hrs 

3 Hrs 

6 Hrs 

9.5 Hrs 

4A 

.5 Hrs 

.8 Hrs 

2 Hrs 

4 Hrs 

8 Hrs 

5A 

NA 

.6 Hrs 

1.4 Hrs 

3 Hrs 

7 Hrs 

6A 

NA 

.4 Hrs 

1 Hrs 

2 Hrs 

4 Hrs 

The recharge table below gives approximate recharge times for different loads and battery sizes.  The table is based on 
batteries depleted to battery cut-off and recharged back to approximately 90% capacity. 
 
 
 