![Securiton ASD 531 Скачать руководство пользователя страница 67](http://html1.mh-extra.com/html/securiton/asd-531/asd-531_technical-description_1231926067.webp)
Installation
ASD 531, Technical description, T 140 416 en
67 / 105
6.5.2
Terminal assignment for eXtended Line Module XLM 35
XLM
terminal
Signal
Wiring
L1
Data A
Addressable loop
according to
or
(see also Sec. 8.5.5)
C1
GND A
G1
Screen
L2
Data B
Addressable loop
according to
or
(see also Sec. 8.5.5)
C2
GND B
G2
Screen
6.5.3
Terminal assignment for RIM 36 Relay Interface Module
RIM terminal
Signal
Wiring
1
Rel. 1
“NO”
Pre-signal 1
Local info or
connection to FACP input
2
“NC”
3
“COM”
4
Rel. 2
“NO”
Pre-signal 2
5
“NC”
6
“COM”
7
Rel. 3
“NO”
Pre-signal 3
8
“NC”
9
“COM”
10
Rel. 4
“NO”
Smoke sensor fault /
Dust smoke sensor /
Smoke sensor dirt
11
“NC”
12
“COM”
13
Rel. 5
“NO”
Fan fault /
Sampling tube /
Pipe breakage sampling tube
14
“NC”
15
“COM”