![Securiton ASD 531 Скачать руководство пользователя страница 79](http://html1.mh-extra.com/html/securiton/asd-531/asd-531_technical-description_1231926079.webp)
Commissioning
ASD 531, Technical description, T 140 416 en
79 / 105
7.3.8
Logging off additional modules XLM 35, RIM 36 and the SD memory card
The additional modules (XLM 35, RIM 36) and the SD memory card are automatically detected when the device is switched
on; from that point onwards, they are monitored and fully functional. The SD memory card begins with data logging, recognis-
able on the flashing
Com
LED on the AMB. To eject the SD memory card or remove a subsequently fitted additional module
(e.g. because it is not being used), the additional modules and SD memory card must first be logged off via the AMB 31 main
board.
Notice
A time-out (approx. 15 s) is configured for the logoff procedure. During this time the additional modules can be
electrically disconnected from the AMB 31 trouble-free or the SD memory card can be removed from the ASD. If
no component is removed during that time (including removing the SD memory card), the additional modules are
re-activated and data logging continues.
Measure
Indicator
Procedure / remarks
(1)
Turn rotary switch “
Mode
” to position
“
6
”
--
(2)
Press key “
Set/Res
”
Airflow LED bar flashes
•
Start logoff procedure, duration approx. 15 s
(3)
Electrically disconnect (ribbon cable)
the relevant additional module from
the AMB 31 within the logoff time
(15 s) or remove the SD memory
card.
Airflow LED bar flashes
•
If the module is not electrically disconnected from
the AMB 31 within 15 s (including removal of the
SD memory card), it is re-activated and data log-
ging continues.
(4)
Turn rotary switch “
Mode
” to position
“
1
”
--
(5)
Press key “
Set/Res
”
--
•
Put ASD into operating state again
7.3.9
Switch device inactive
This function switches off the fan and sensor of the ASD 531. The ASD 531 is then no longer capable of an alarm. An inactive
ASD triggers a fault and signals the superordinate unit (FACP) accordingly. On the ASD the “
Fault
” LED is then continuously
lit.
Switch device inactive
Measure
Indicator
Procedure / remarks
(1)
Turn rotary switch “
Mode
” to position
“
7
”
--
(2)
Press key “
Set/Res
”
Fault
LED lit:
•
Device is inactive
•
Device triggers fault
Activate device again
Measure
Indicator
Procedure / remarks
(1)
Turn rotary switch “
Mode
” to position
“
1
”
Fault
LED lit:
(2)
Press key “
Set/Res
”
--
•
Device is again in operation mode